NEW YORK CITY 

2011 
ELECTRICAL CODE 



(Administrative Provisions and 2008 NEC® Amendments) 



New York City 2011 Electrical Code 



NEW YORK CITY 2011 ELECTRICAL CODE 

(Administrative Provisions and 2008 NEC® Amendments) 

TABLE OF CONTENTS 

SECTION 1: PREFACE v 

SECTION 2: ACKNOWLEDGEMENTS vii 

SECTION 3: ADMINISTRATIVE REQUIREMENTS 1 

SECTION 4: TECHNICAL REQUIREMENTS 25 



New York City 2011 Electrical Code m 



iv New York City 2011 Electrical Code 



PREFACE 

Adopted in 1915, the New York City Electrical Code reflected the first set of codified electrical 
standards in the United States. This modern code provided a foundation that helped spur the growth our 
City experienced over the next century. As the last century drew to a close, however, the existing 
Electrical Code had become increasingly unwieldy and outdated. Despite substantial changes and 
improvements in electrical technology, the code had not undergone a major revision since its 1987 edition. 
Local Law 64 of 2001 addressed these shortcomings of the Elec ^al Code by replacing it with the 
1999 National Fire Protection Association's National Electrical Code (NEC ), NJ-FA m . ine 
legislation required periodic revision of the Code's technical provisions ensuring that the Code will 
always be up-to-date and reflect the latest standards. It was followed by Local Law 41 of 2002, a 
prerequisite to completing the new Code, as it adopted amendments tailoring the NEC to the specific 
needs of the City's high-density urban environment. The first revision in this ^ n ^ e ™ ^ 
Law 81 of 2003, which adopted NEC 2002 with amendments. Local Law 49 of 2006, adopting NEC 
2005 with amendments, followed three years later. 

This legislation, NYC Local Law 39 of 2011, amends the New York City Administrative Code to 
adopt amendments to the 2008 edition of the NEC; NFPA 70. The amendments again adapt the revised 
national standards to the special requirements of building and construction in the City of New York and 
apply to work performed on and after July 1 , 201 1 . 

The Department thanks those committees that function as the vehicle for the required periodic 
review of the NEC and the source of proposed local amendments. Under the Electrical Code Revision 
and Interpretation Committee, panels were formed to review new NEC 2008 technical provisions. The 
panels' work-product was then reviewed by the full committee. An additional panel was also established 
to review the administrative sections of the City's Electrical Code, including licensing permitting and 
enforcement. The Electrical Code Advisory Committee is the managing committee for the process, 
ultimately reviewing the proposed technical and administrative changes and advising the Commissioner 
on their adoption. These Committees and panels include the regulating City agencies and representatives 
from all sectors of the electrical industry, including labor, real estate, design professionals, and 
manufacturers. These committees were designed to make the Electrical Code revision an inclusive and 
cooperative process. Every effort has been made to ensure that input is received from all stakeholders 
and this product would not have been possible without their time and contribution. 



National Electrical Code®, NEC®, NFPA 70® and the NEC Symbol are registered trademarks of the National Fire Protection 
Association, Quincy, MA 02169 



New York City 2011 Electrical Code 



VI "" " ■ — 

New York City 201 1 Electrical Code 



ACKNOWLEDGEMENTS 

We would like to thank the people who have played a role in creating the New York City 2011 
Electrical Code. The hard work, professionalism, and commitment of the Electrical Code Advisory 
Committee (E.C.A.C.), the Electrical Code Revision and Interpretation Committee (E.C.R.I.C), 
Committee Panels, and the staff of the Department of Buildings, the Mayor's Office of City Legislative 
Affairs, the City Council, and other city agencies, have ensured that the people of the City of New York 
will continue to enjoy the benefits of up-to-date electrical code standards. 

DEPARTMENT OF BUILDINGS 

Robert D. LiMandri, Commissioner 

FatmaAmer, P.E., First Deputy Commissioner 

Thomas Fariello, R.A., Acting First Deputy Commissioner 

Phyllis Arnold, Deputy Commissioner 

Stephen Kramer, Senior Counsel 

James Colgate, R.A., Assistant Commissioner 

Benjamin Jones, PMP, Assistant Commissioner 

Chantal Senatus, Assistant General Counsel 

Bonnie Gerard, Sr. Project Manager 

John Bosse Leonard Leitner 

Jack Bunk John Lee 

Paul Cammareri Sam Marcovici 

Frank Coluccio Winston McKenzie 

Robert Diamond Edwin Pemberton 

Helen Gitelson Donald Ranshte 

Danielle Grillo Michael Rogalewski 

Ida Dias-Hall Sharima Singh 

Neil Isaac Deborah Taylor 

Severiano John Kin Wong 

CITY AGENCIES 

Eduardo L. Crosa, Senior Counsel, NYC Law Dept. 

Steven Goulden, Senior Counsel, NYC Law Dept 

Christopher Afuw ah, FDNY 

Shaji Joseph, FDNY 

Mark Smith, FDNY 

CONSOLIDATED EDISON OF NEW YORK 

John Esemplare 

Ralph Esemplare 

Bayly M. Tyler 

COVER DESIGN 

Rachel Richards 



New York City 2011 Electrical Code 



CODE PANELS 

Panel Leaders: 

Richard Boll, Alburdan Electric Co. Inc; Robert L'Insalata, P.E., AKF Engineers, LLP; 

Frank Lorenz, P.E., AKF Engineers, LLP; Sam Marcovici, USEE, Department of Buildings; 

Glen Neville, P.E., Deutsche Bank(REBNY); Chantal Senatus, Esq., Department of Buildings; 

Richard Sobel, P.E, Quantum Electric Corporation 



Members: 

Chris Afuwah, Fire Department of the City of New York 
Julius Bogad, P.E., Jaros, Baum & Bolles 
David Buckner, Solar Energy Systems 
Serge Budzyn, P.E., Lilker Associates 
Jack Bunk, Department of Buildings 
John Cangemi, Underwriters Laboratories 
Scott Cohen, Electrical Training Course 
Frank Coluccio, Department of Buildings 
Lou Cotroneo, Five Boro Electrical Assoc. 
Sal Ferrara, Electrical Training Center 
Peter Greene, Department of Buildings 
Ida Dias-Hall, Department of Buildings 
Neil Isaac, Department of Buildings 
Shaji Joseph, Fire Department of the City of New York 
Vincent Logozzo, Abilene Electric Inc. 
Ciro Lupo, National Electrical Contractor: Assoc, NY 
Vincent McElroen, Local Union No. 3, International 
Brotherhood of Electrical Workers 



Richard McFadden, Jaros, Baum & Bolles 

Brian McGovern, Verizon 

Winston McKenzie, Department of Buildings 

Walter Mehl, Jaros, Baum & Bolles 

Rick Miller, Contact Power Inc. 

Gil Moniz, National Electrical Manufacturing Assn. 

William Moore, Museum of Modern Art 

Anthony Pereira, Alt Power Inc. 

Chris Rogan, Cutler Hammer 

Deborah Taylor, Department of Buildings 

Mark R. Torre, Jaros, Baum & Bolles 

James Trainor, Verizon 

Clarence Tsung, Adjunct Asst. Professor New York 
University 

John E. Villafane, Eldor Electric LLC 
Harry Vyas, Department of Buildings 
Willard Warren, P.E., Willard Warren Associates 
Joseph Zee, Electrotech 



ELECTRICAL CODE ADVISORY COMMITTEE 

Phyllis Arnold, Esq., Chair 

Chantal Senatus, Esq., Vice Chair 

Bonnie Gerard, Sr. Project Manager 



Members: 



SalAnelli, Association of Electrical Contractors 
Phyllis Arnold, Esq., Department of Buildings 
Kuba Brown, Local 94, International Brotherhood of 

Electrical Workers 
Jack Bunk, Department of Buildings 
Marolyn Davenport, Real Estate Board of New York 
John Esemplare, Con Edison 
Bonnie Gerard, Department of Buildings 
Helen Gitelson, Department of Buildings 
Ida Dias-Hall, Department of Buildings 
Benjamin Jones, Department of Buildings 
Leonard Leitner, Department of Buildings 



Edwin Lopez, New York Electrical Contractors Assn. 
Frank Lorenz, P.E., AKF Engineers, LLP 
Sam Marcovici, Department of Buildings 
Brian McGovern, Verizon 

Raymond Melville, Local 3, International Brotherhood of 

Electrical Workers 
Pat Pescatore, 5 Boro Electrical Contractors Association 
Chantal Senatus, Esq., Department of Buildings 
MarkE. Smith, Fire Department of the City of New York 
Deborah Taylor, Department of Buildings 
James Trainor, Verizon, CWA Local 1101 



New York City 2011 Electrical Code 



ELECTRICAL CODE REVISION and INTERPRETATION COMMITTEE 

Co Chairs: 

Chantal Senatus, Esq., Asst General Counsel 
Sam Marcovici, MSEE 



Members 



Chris Afuwah, Fire Department of the City of New York 

Julius Bogad, P.E, Jaros, Baum & Bolles 

Richard Boll, Alburdan Electric Co. Inc. 

Jack Bunk, Department of Buildings 

John Cangemi, Underwriters Laboratories Inc. 

Frank Coluccio, Department of Buildings 

John Esemplare, Con Edison 

Bonnie Gerard, Department of Buildings 

Ida Dias-Hall, Department of Buildings 

David Harron, Association of Electrical Contractors 

Neil Isaac, Department of Buildings 

John Kenny, International Association of Electrical 

Inspectors 
Robert Ulnsalata, P.E., AKF Engineers, LLP 
Frank Lorenz, P.E., AKF Engineers, LLP 



Vincent McElroen, Local Union No. 3, International 

Brotherhood of Electrical Workers 
Winston McKenzie, Department of Buildings 
Rick Miller, Contact Power Inc. 
MohamedA. Mohamad, M. A. M. Electrical Corp 
GHMoniz, National Electrical Manufacturing Association 
Glen Neville, P.E, Deutsche Bank, (REBNY) 
Anthony Pereira, Alt Power Inc. 
Alvin Sauherman, Jubilee Electric Co. Inc. 
Richard Sobel, P.E., Quantum Electric Corporation 
Deborah Taylor, Department of Buildings 
Clarence Tsung, Adjunct Asst. Professor New York 

University 
Willard Warren, P.E., Willard Warren Associates 
Joseph Zee, Electrotech 



Effective Date of NYC Local Law 39 of 2011 



§14. (a) This local law shall take effect on July 1, 2011, except that the provisions of subdivision j of section 27-3018 as 
set forth in section nine of this local law and section 27-3021.2 as set forth in section eleven of this local law shall take effect 
on March 1, 2012, provided that the commissioner of buildings shall take all actions necessary for implementation of this 
local law, including the promulgation of rules, prior to each such effective date. 

(b) Phase-in period of new standards for electrical work. During the period from July 1, 2011 through December 31, 
201 1 (the phase-in period), electrical work may be performed either in accordance with the electrical code technical standards 
adopted pursuant to section 27-3024 and section 27-3025 of the administrative code of the city of New York, as enacted by 
section 12 and section 13, respectively, of this local law, or in accordance with the standards set forth in chapter 3 of title 27 
of such code in effect prior to July 1, 2011, at the option of the licensed master or special electrician or other authorized 
person performing the work. 

(c) A copy of the 2008 edition of the National Fire Protection Association NFPA 70 National Electrical Code, 
incorporated by reference into this local law, shall be kept on file by the City Clerk with this local law and shall be available 
for public inspection. 



New York City 2011 Electrical Code 



IX 



We give special thanks and recognition 
to our elected officials for their support of 
Local Law 39 of 2011 



NYC Local Law 39 of 2011 

Michael R. Bloomberg, Mayor 
Christine Quinn, Speaker of the City Council 

The Council of the City of New York 

Housing and Buildings Committee 

Erik Martin Dilan, Chair, 37th District 

Gale A. Brewer, 6 th District 

Leroy G Comrie, Jr., 27 th District 

Elizabeth Crowley, 30 th District 



Lewis A. Fidler, 46 th District 

James F. Gennaro, 24 th District 

Robert Jackson, 7 th District 

Letitia James, 35 th District 

Brad Lander, 39 th District 

Melissa Mark-Viverito, 8 th District 

Rosie Mendez, 2 nd District 

James S. Oddo, 50 th District 

Joel Rivera, 15 th District 

Eric Ulrich, 32 nd District 

Jumaane D. Williams, 45 th District 

Legislation Sponsors 

Erik Martin Dilan, Chair, 37th District 

James F. Gennaro, 24 th District 

Sara M. Gonzalez, 38 th District 

Robert Jackson, 7th District 

Peter Koo, 20th District 

Eric Ulrich, 32nd District 

Mark Weprin, 23rd District 

City Council Staff 

Robert Newman 

Baaba Halm 

RickArbelo 

Benjamin Goodman 

Jeffrey Haberman 

Laura Rodgers 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



ADMINISTRATIVE CODE SECTIONS OF THE 
NEW YORK CITY ELECTRICAL CODE 

ADMINISTRATIVE CODE OF 
THE CITY OF NEW YORK 

Title 27 Construction and Maintenance 
Chapter 3 Electrical Code 

§27-3001 Short title. This chapter shall be known and may be cited as the "electrical code." 

§27-3002 Purpose. Since there is danger to life and property inherent in the use of electrical energy, 
the electrical code is enacted to regulate the business of installing, altering or repairing wiring and 
appliances for electrical light, heat, power, signaling, communication, alarm or data transmission in the 
city of New York and the licensing of all persons who engage in such business. 

§27-3003 Construction. This chapter shall be liberally construed to accomplish its purpose. Words 
used herein which have acquired a particular meaning in the usage of the electrical trades shall be 
construed as understood in the trade. 

§27-3004 Definitions. Unless otherwise expressly stated, the following terms, whenever used in this 
chapter or in any rule or reference standard promulgated pursuant to this chapter, shall mean: 

CITY AGENCY: A city, county, borough, or other office, position, administration, department, 
division, bureau, board or commission, or a corporation, institution or agency of government, the 
expenses of which are paid, in whole or in part, from the city treasury. 

COMMISSIONER: The commissioner of buildings. 

DEPARTMENT: The department of buildings. 

DIRECT EMPLOY: Direct employment shall be evidenced by payroll records, such as social 
security payments, income tax withholding or the disbursement of other funds as required by law for the 
benefit of such employee, timekeeping records, such as time cards and sign-in sheets, work orders, and 
assignment or route logs. 

DIRECT SUPERVISION: Control exercised by a licensed individual, either personally or through 
one or more demonstrated levels of competent supervision over individuals (i) in the direct employ of a 
master electrician's business or (ii) in the direct employ of an individual, partnership, corporation or city 
agency employing a special electrician. Direct supervision includes field inspection, supervision of job 
sites, and the maintenance of records of such supervision and such other records required by the 
commissioner. 

ELECTRICAL WORK: The installation, alteration, maintenance, or repair of electric wires and 
wiring apparatus and other appliances used or to be used for the transmission of electricity for electric 
light, heat, power, signaling, communication, alarm or data transmission. 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



EMPLOYEE: An individual who is on the payroll of an employer and who under the usual common 
law rules applicable in determining the employee-employer relationship has the status of an employee. 
Such term shall not include an independent contractor. 

JOURNEYMAN ELECTRICIAN: An individual who has demonstrated a progressive 
understanding, proficiency and competence in the electrical trade, which shall include: 

a. A working familiarity with the electrical code and the electrical code technical standards and 
the ability to apply the code requirements correctly; 

b. The application of basic electrical theory and the utilization of trade math skills on the job site; 

c. A working knowledge of the tools of the trade and the ability to utilize them properly; and 

d. An ability to draft simple diagrams and interpret from drawings for the purpose of the 
installation, alteration or repair of electric wiring or appliances for light, heat and power. 

LOW VOLTAGE ELECTRICAL WORK: The installation, alteration, maintenance or repair of 
electrical wiring that is designed to operate at less than fifty volts for signaling, communication, alarm, 
and data transmission circuits except that such term shall not include the installation, alteration, 
maintenance or repair, regardless of voltage, of any such wiring which connects to, is a part of or is 
located within: 

(a) life safety systems as defined by rule of the commissioner, including but not limited to (i) 
those safety systems and features listed in subparagraphs a through n of paragraph three of 
subdivision a of section 27-228.2 of the administrative code and (ii) alarm and extinguishing systems 
subject to building code reference standards RS 17-3, RS 17-3A, RS 17-3B, and/or RS 17-3C, 

(b) class I, II or III hazardous locations as described in the electrical code technical standards, 
including but not limited to certain areas within commercial garages as set forth therein, aircraft 
hangers, gasoline dispensing and service stations, bulk fuel storage plants and facilities which may 
be utilized for spray applications or for a dipping and coating process, 

(c) intrinsically safe systems as described in the electrical code technical standards, or 

(d) a point of connection to or interfacing with a control circuit which activates light, heat or 
power circuits. 

LOW VOLTAGE INSTALLER: An individual who is certified by the commissioner to act as the 
representative of a business entity authorized pursuant to this chapter and the rules of the department to 
perform low voltage electrical work in or on any building, premises or lot in the city. An individual so 
certified shall have full responsibility on behalf of such business entity for the manner in which such 
work is done and for the selection, supervision and control of employees of such business entity who 
perform such work. Such individual shall be an employee of the business entity which he or she 
represents and shall supervise, direct and be responsible for only the work of the employees of such 
business entity. Such individual shall not represent more than one business entity. 

MASTER ELECTRICIAN BUSINESS: A sole proprietorship, partnership or corporation 
authorized by the commissioner to engage in or carry on, as an independent contractor and as its regular 
business, the business of performing electrical work in or on any building, premises or lot in the city 
under a license issued to a master electrician. 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



MASTER ELECTRICIAN'S LICENSE: The license issued to an individual who has passed the 
required examination and tests and who otherwise qualifies for the issuance of such license pursuant to 
this chapter. An individual who holds such license shall be known as a master electrician. 

RESPONSIBLE REPRESENTATIVE: A master electrician who has the authority to make final 
determinations and who has full responsibility on behalf of a master electrician business for the manner 
in which electrical work is done and for the selection, supervision and control of all employees of such 
business who perform such work. A partnership or corporation shall designate one master electrician 
who is a partner of such partnership or an officer of such corporation to be the responsible representative 
of such partnership or corporation. The proprietor of a sole proprietorship shall be the responsible 
representative of such sole proprietorship. A master electrician shall not be the responsible 
representative of more than one partnership or corporation and shall file for, supervise, direct and be 
responsible for only the work of such partnership or corporation. If the master electrician business is in 
the form of a sole proprietorship, only the master electrician who owns such business shall be the 
responsible representative of such business and shall file for, supervise, direct and be responsible for 
only his or her own work and the work of his or her employees. Notwithstanding the foregoing 
provisions, where the department has issued a violation notice for work performed by an unlicensed 
person or work performed without the required permit and where such work is otherwise in compliance 
with the electrical code and the electrical code technical standards, a responsible representative may file 
an application for a permit or take any other actions with respect to such work directed by the 
department to address the violation. 

SPECIAL ELECTRICIAN'S LICENSE: The written authorization of the commissioner to an 
individual who is an employee of an individual, a partnership or a corporation owning, leasing or 
managing a building, buildings or parts thereof to perform electrical work in or on specific buildings, 
lots or parts thereof owned, leased or managed by such individual, corporation or partnership. An 
individual who has obtained such authorization shall be known as a special electrician. A special 
electrician shall determine the method of doing the work in or on such buildings and shall have sole 
responsibility for supervising and directing the employees of such owner, lessee or manager who 
perform such work. A special electrician shall not supervise the work of individuals who are not 
employees of the owner, lessee or manager of the buildings on which the special electrician is 
authorized by his or her license to perform electrical work. A special electrician's license shall not 
authorize the holder to engage in or carry on the business of performing electrical work as an 
independent contractor. 

SPECIAL PERMISSION: The written approval of the commissioner in circumstances involving the 
exercise of his or her discretion and in circumstances not covered by this chapter. 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



§27-3005 Jurisdiction, powers and duties of the commissioner. 

a. The commissioner is authorized to exercise all powers necessary to enforce the electrical code 
and the electrical code technical standards, including but not limited to the power to: 

1. Promulgate rules respecting the installing, altering, maintaining or repairing of (i) electric 
wires and wiring apparatus and other appliances used or to be used for the transmission of electricity 
for electric light, heat, power, signaling, communication, alarm or data transmission and (ii) low 
voltage electrical wiring in or on any building, premises or lot in the city of New York. 

2. Cause any wiring or appliances for electrical light, heat or power to be examined and 
inspected, and the approval thereof to be certified in writing, 

(a) by an officer or employee of the department designated by him or her for that purpose, or 

(b) by any inspection agency certified by the commissioner in accordance with rules 
promulgated by the commissioner, or 

(c) when such wiring or appliances are located in a building owned by the city or any city 
agency, (i) by a licensed professional engineer, or (ii) by a person with a baccalaureate degree in 
electrical engineering, or (iii) by any person who holds the job title of electrical inspector or any 
job title equivalent thereto, as classified by the commissioner of citywide administrative services 
pursuant to section eight hundred fourteen of the charter; provided, however, that such licensed 
professional engineer or person with a baccalaureate degree in electrical engineering or person 
holding the job title of electrical inspector shall not have performed the work to be inspected and 
shall be an officer or employee of the city agency which contracted for such work. 

3. Order the remedying of any defect or deficiency in the installing, altering or repairing of 
electric wires and wiring apparatus and other appliances used or to be used for the transmission of 
electricity for electric light, heat, power, signaling, communication, alarm or data transmission. 

4. Cause any order issued by him or her which has not been complied with to be enforced and to 
take any civil or criminal proceedings or actions for its enforcement. 

5. Order any person or corporation engaged in supplying electrical energy to discontinue such 
supply as specified in such order if the wiring or appliances for electric light, heat, power, signaling, 
communication, alarm or data transmission shall be dangerous to persons or property therein. 

6. (a) Promulgate rules fixing the date, scope and subject matter of examinations of applicants 
to become licensed as master electricians and special electricians and, upon recommendation of the 
license board, promulgate rules respecting the issuance, suspension and revocation of such licenses. 

(b) Promulgate rules fixing the date, scope and subject matter of examinations of applicants 
for certification as low voltage installer and respecting the issuance, suspension and revocation 
of such certification. 

7. Appoint, in accordance with the rules of the department and at his or her discretion, special 
boards or committees to provide advice or assistance in the implementation, interpretation, variation 
or amendment of any provision of the electrical code or the electrical code technical standards or anv 
rule promulgated pursuant to this chapter. 

8. Promulgate rules regarding the issuance of approvals for the use of electrical appliances and 
materials and the granting of special permission to use wiring or appliances in cases involving the 
exercise of his or her discretion and in cases not covered by this chapter. 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



9. Designate as prescribed in section 14-106 of title fourteen of the code, with the consent of the 
police commissioner, certain electrical inspectors as special patrolmen of the police department. 
Such special patrolmen shall possess powers to perform the duties of and be subject to the orders, 
rules and regulations of the police department in the same manner as regular patrolmen. Each 
special patrolman shall have a badge and card, as furnished by the police department. He or she 
shall have power to issue summonses returnable in the New York city criminal court, covering 
violations of this chapter. 

b. The foregoing provisions are detailed statements of certain powers possessed by the commissioner 
and shall not be construed as limiting his or her authority. 

§27-3006 Federal and state buildings. Nothing in this chapter shall be construed to apply to any 
building, the electrical equipment of which is under the control of the United States of America or the 
state of New York or of any department, bureau or office thereof. 

§27-3007 City departments. The various departments, boards and offices of the city shall be subject 
to the provisions of this chapter. 

§27-3008 Public service corporations. 

a. Except as provided for in subdivision b of this section, the provisions of this chapter shall not 
apply to: 

1. Electrical equipment used exclusively for the operation of railroads, railways and trackless 
trolleys, or 

2. Installations, including associated lighting, under the exclusive control and use of electric 
utilities for the purpose of communications, metering, generation, control transformation, 
transmission or distribution of electric energy. Such installations shall be located in buildings used 
exclusively by utilities for such purpose, in buildings in enclosures containing only metering 
equipment, outdoors on property owned or leased by the utility, on public highways, streets or roads 
or outdoors on private property by established rights such as easements, or 

3. Communication equipment used exclusively for communicating or signal purposes provided 
that such equipment is installed by and under the exclusive control and use of communications 
utilities subject to the jurisdiction of the public service commission and is located outdoors or in 
building spaces used only for such equipment. 

b. The provisions of this chapter shall apply to such portions of commercial, industrial or office 
buildings owned or leased by the above mentioned persons or corporations, not used for the operations 
of such persons or corporations, such as public spaces leased or rented to other persons or corporations. 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



§27-3009 Master electrician's and special electrician's license board. 

a. For each calendar year, the commissioner shall appoint a board to review the character and fitness 
of applicants for a master electrician's or special electrician's license and the approval of master 
electrician businesses, to advise the commissioner regarding allegations of illegal practices on the part of 
master and special electricians or master electrician businesses, to investigate and report on all proposed 
suspensions or revocations of licenses and approvals of master electrician businesses and all proposed 
penalties, and to perform any other responsibilities as may be requested by the commissioner and as set 
forth in rules promulgated by the department. The commissioner may, for good cause shown, remove 
any member thereof and shall fill any vacancy therein, which board shall consist of: 

1. Two officers or employees of the department. 

2. Two licensed master electricians actively engaged in the trade. 

3. A journeyman electrician. 

4. An electrical inspector in the employ of an inspection agency certified by the commissioner. 

5. An electrician in the employ of a public service corporation of the city. 

6. A registered architect or licensed professional engineer of at least five years experience. 

7. A real estate owner or manager. 

b. A member of the board who is an officer or employee of the department shall serve as 
chairperson and all members shall serve without compensation. Five members including the chairperson, 
who shall be entitled to vote, shall constitute a quorum of the board for the transaction of business; but 
no recommendation for the issue, modification, suspension or revocation of a license or of a proposed 
penalty shall be adopted except by the vote of at least five members of the board. 

c. The license board shall investigate the character and fitness of all applicants for licenses who 
shall have passed the required examination and shall report to the commissioner the results of such 
examination. It shall investigate and hear all written complaints against holders of such licenses and 
master electrician businesses and report to the commissioner its findings and recommendations. It shall 
keep minutes of its proceedings and hearings and records of its investigations and examinations of 
applicants for licenses and approvals of master electrician businesses. Upon the holding of any hearing, 
the chairperson of the board presiding at such hearing may administer oaths, and the board may issue 
and cause to be served subpoenas requiring the attendance of witnesses and the production of books and 
papers pertinent to any hearing held by it upon written complaint. Such subpoenas shall be signed by the 
commissioner and the fees and mileage paid to witnesses upon the service of such subpoenas shall be 
those prescribed in section fifteen hundred thirty-nine of the civil practice law and rules. 

§27-3010 Qualification and Examination of applicants for master electrician's and special 
electrician's licenses. 

a. Qualification of Applicant. An applicant for a license as a master electrician or special electrician 
must be over the age of twenty-one years, of good moral character and, at the time of applying for 
examination, shall have had, during the ten (10) years immediately preceding his or her application, at 
least seven and one-half (7 1 / 2 ) years or the equivalent as indicated below and during such time a 
minimum of ten thousand five hundred (10,500) hours or the equivalent as indicated below of 
satisfactory experience in the installation, alteration and repair of wiring and appliances for electric light, 
heat and power in or on buildings or comparable facilities. Except as otherwise provided below, such 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



satisfactory experience must have been obtained while under the direct supervision of a licensed master 
electrician or special electrician or, with respect to experience outside the city, under the direct 
supervision of an individual with comparable qualifications as determined by the commissioner, and 
while in the employ of (i) a master electrician business as defined herein, or (ii) an individual, a 
partnership or a corporation owning, leasing or managing a building, buildings or parts thereof and 
employing a special electrician to perform electrical work in or on specific buildings, lots or parts 
thereof owned, leased or managed by such individual, corporation or partnership, or (iii) an individual, a 
partnership or a corporation deemed acceptable by the commissioner. No more than twenty-five percent 
(25 %) of such satisfactory experience shall have been gained while working outside the United States 
unless the commissioner determines that the licensing system and electrical code of the foreign 
jurisdiction is essentially similar to licensing systems and electrical codes in the United States. The 
following shall be deemed to fulfill the satisfactory experience requirement: 

1. A journeyman electrician who has worked at least seven and one-half {IV2) years and during 
such time a minimum often thousand five hundred (10,500) hours of such experience must have 
been obtained by working with his or her tools on the installation, alteration and repair of wiring and 
appliances for light, heat and power in or on buildings or comparable facilities, or 

2. A graduate of a college or university who holds a degree in electrical engineering, either a 
master of science (M.S.) or bachelor of science (B.S.) and has in addition worked at least (i) with 
respect to an applicant with an M.S. degree, two and one-half (214) years and during such time a 
minimum of thirty-five hundred (3500) hours of such experience or, (ii) with respect to an applicant 
with a B.S. degree, three and one-half ( V/i) years and during such time a minimum of forty-nine 
hundred (4900) hours of such experience must have been obtained by working with his or her tools 
on the installation, alteration and repair of wiring and appliances for electric light, heat and power in 
or on buildings or comparable facilities, or 

3. A graduate of a vocational, industrial, trade school, or apprenticeship program registered with 
the New York state department of labor, specializing in electrical wiring, installation and design or 
applied electricity, who has worked at least five and one-half (SVi) years and during such time a 
minimum of seventy-seven hundred (7700) hours of such experience must have been obtained by 
working with his or her tools on the installation, alteration and repair of wiring and appliances for 
electric light, heat and power in or on buildings or comparable facilities, or 

4. Any person who attended courses in a college or university leading to a degree in electrical 
engineering, mechanical engineering, bachelor of science in electrical engineering or mechanical 
engineering, who passed all subjects in the required courses shall be credited with satisfactory 
experience equal to fifty per cent (50%) of the number of curricula years he or she has satisfactorily 
completed which, in no event, however, shall exceed two and one-half (214) years credit of 
satisfactory experience, the balance of the required seven and one-half (7 Vi) years, i.e., five (5) years 
and during such time a minimum of seven thousand (7000) hours of such experience must have been 
obtained by working with his or her tools on the installation, alteration and repair of wiring and 
apparatus for light, heat and power in or on buildings or comparable facilities, or 

5. Any person who attended courses in a vocational, industrial or trade school, registered with 
the New York state department of labor, specializing in electrical wiring, installation and design or 
applied electricity who has passed all subjects in the required courses shall be credited with fifty per 
cent (50%) of the number of curricula years that he or she has satisfactorily completed which, 
however, in no event, shall exceed two (2) years credit of such experience, the balance of the 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



required seven and one-half (IV2) years, i.e., five and one-half (SVi) years of such experience and 
during such time a minimum of seventy-seven hundred (7700) hours must have been obtained by 
working with his or her tools on the installation and repair of wiring for electric light, heat and 
power in or on buildings or comparable facilities, or 

6. An employee of a government agency, private inspection agency or other entity, acceptable to 
the commissioner, whose duties primarily involve the inspection of electrical work for compliance 
with the electrical code and the electrical code technical standards and/or other laws relating to the 
installation, alteration or repair of electrical wiring or appliances shall be credited with fifty percent 
(50%) of the number of years that he or she has been satisfactorily employed in such duties within 
the ten (10) year period prior to application, which, however, in no event, shall exceed two and one- 
half (2 V2) years credit of satisfactory experience. The balance of the required seven and one-half (7 
Vi) years, i.e., five (5) years and during such time a minimum of seven thousand (7000) hours of 
such experience must have been obtained by working with his or her tools on the installation, 
alteration and repair of wiring and appliances for electric light, heat and power in or on buildings or 
comparable facilities except that the requirement of subdivision a of this section that an applicant's 
working experience must have been within the ten (10) year period prior to application shall not 
apply to such balance of five (5) years working experience required pursuant to this paragraph. 

b. Examination of Applicant. 

1. Every application for a master electrician's or special electrician's license shall be made in 
writing in such form and shall furnish such information as the commissioner may, from time to time, 
prescribe, and set forth in the rules of the department. It is a condition of the license that information 
in the application be kept correct and current. Any change in required information that occurs prior 
to the issuance of the license shall be reported to the department within fourteen days of the change. 

2. Every applicant shall be required to take an examination in accordance with the rules of the 
department. However, where the application is on behalf of a city agency, the commissioner may 
waive the examination requirement if the applicant has sufficient experience qualifications of a type 
and duration comparable to those set forth in subdivision a of this section as determined by the 
commissioner. 

3. Every applicant shall submit to such investigation by the license board as may be proper to 
determine the applicant's character and fitness. Every applicant shall commence the application 
process with the department within one year of passing the examination for licensure and shall 
furnish to the department a completed application within one year of submission of the first filing. 
Failure to provide all requested documents in a timely manner will constitute an incomplete 
application and may result in denial of the license. 

4. Every applicant shall be required to submit such documentation as is required to establish a 
place of business within ninety days after the license board's recommendation that the applicant has 
the required character and fitness for licensure. Where all requested documents are not provided in a 
timely manner an application will be deemed incomplete and may result in the denial of the license. 

§27-3011 Repealed by Local Law 64 of 2001 

§27-3012 Repealed by Local Law 64 of 2001 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



§27-3013 Business establishments and master electricians. 

a. Place of Business, generally. 

1 . Every master electrician business shall at all times have a place of business at a specified 
address in the city at which the licensee may be contacted by the public and the department by mail, 
telephone or other modes of communication, located in a business zone in conformity with the 
zoning regulations and kept open during the usual business hours unless other means acceptable to 
the commissioner is provided. 

2. At such place of business, there shall at all times be prominently displayed a permanent sign 
of a minimum size of one hundred fifty square inches, stating the name of such license holder, the 
license number of such licensee, and the words "licensed electrician" or "licensed electrical 
contractor" on a plate glass window and the name of the master electrician business if different than 
the name of the license holder; or an outside sign of permanent construction fastened and readily 
visible to pedestrians; or if such place of business be an office, commercial or industrial building, the 
names shall be indicated on the entrance door of the particular portion of the premises or on a 
bulletin board on the main floor. 

3. All business vehicles, advertising, websites and stationery used in connection with electrical 
work required to be performed under a license issued to a master electrician shall display 
prominently the words "N.Y.C. Licensed Electrician," the license number of the responsible 
representative of such business and of all other master electricians associated with such business, the 
authorization number of the master electrician business and the business address. If the business is 
conducted under a trade name, or is a partnership or corporation, the trade name, partnership, or 
corporate name shall contain the root word "electric" and be displayed prominently. 

4. The applicant for approval of a master electrician business under a license issued to a master 
electrician shall have filed with the commissioner, in such form as the commissioner may direct, 
proof that such applicant carries all insurance required by law including, but not limited to, workers' 
compensation, disability and - one million dollars of general liability insurance listing the 
Department as certificate holder, and that the applicant business is financially responsible. Each 
policy of insurance shall contain a provision of continuing liability notwithstanding any recovery 
under such policy. 

5. The applicant shall indicate the name and license number of the master electrician who shall 
serve as the responsible representative of such business, and, if the business is a partnership or 
corporation, the names of all other master electricians associated with such business. Upon approval 
of such application the commissioner shall issue an authorization number to the business. The 
authorization number shall be included on all applications for permits and any other documents 
required to be filed with the department. 

6. The office or other place where the master electrician business is to be conducted may be 
shared by one or more master electrician businesses. However, each business whether in the form of 
a sole proprietorship, partnership or corporation, shall distinguish its identity from any other 
business sharing the same office space. Such distinctions shall be maintained in a manner 
satisfactory to the department. 

b. Business Conduct. 

1 . A master electrician business shall be principally engaged in the business of performing 
electrical work in or on buildings, premises or lots in the city. 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



2. In the case of a partnership or corporation, a master electrician's license may be separately 
held by more than one partner or officer as a representative of such partnership or corporation; 
however, only one master electrician shall be the responsible representative of such corporation or 
partnership. Under no circumstances shall any one licensee represent more than one business at any 
one time. 

3. A master electrician representing a master electrician business shall, during the hours the 
business is engaged in the performance of electrical work, devote his or her full time to the operation 
of such business. 

4. (i) Applications for permits and any other document that the commissioner may require to be 
filed with the department, shall bear the stamp of the master electrician's seal as well as the signature 
of the responsible representative of the master electrician business or, if the business is a partnership 
or corporation, such document may bear the stamp of the seal and the signature of a master 
electrician who files on behalf of such business acting pursuant to a written delegation, filed with the 
department, from the responsible representative of such business. For applications and other 
documents submitted electronically, the digital signature and imprint of the seal may be submitted in 
a manner authorized by the commissioner. 

(ii) The responsible representative of a business may not delegate such authority to a master 
electrician who is not an officer of such corporation or a partner of such partnership. Such 
person shall personally sign applications for permits. The responsible representative of a 
business shall have the authority to make final determinations and shall have full responsibility 
for the manner in which the work is done, except that where work is done under a permit issued 
pursuant to an application bearing the signature and seal of a master electrician acting pursuant 
to a written delegation from the responsible representative of such business, both the responsible 
representative of such business and the master electrician who signed and affixed his or her seal 
to the application for such permit shall be jointly and severally responsible for the manner in 
which the work is done. 

c. Changes to Business. 

1. The holder of a master electrician's license shall report in writing to the license board any change in 
the place of business within thirty (30) days of the change. If such change occurs prior to issuance of the 
license, an applicant shall report the change to the license board within fourteen (14) days of the change. 

2. The approval of a master electrician business is valid only as long as the responsible representative 
identified on the application for approval of the master electrician business actively participates in the 
actual operation of the business. In the event a responsible representative leaves a master electrician 
business, both the representative and the business must notify the license board within thirty (30) days of 
the change. 

(i) A corporation or partnership must notify the license board of the death of a responsible 
representative within thirty (30) days after such death. Failure to do so shall be deemed 
sufficient cause for suspending or revoking the approval to do business of the master electrician 
business or the license of the master electrician. The decedent licensee's legal representative 
may, with the commissioner's consent, retain the licensee's license and seal for the purpose of 
completing all unfinished work of such licensee for which plans have been approved and permits 
issued, provided that such work is performed by or under the direct supervision of a licensed 
electrician. 



1 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



(ii) Except as otherwise provided by rule, a master electrician business whether in the form 
of a corporation, a partnership or a sole proprietorship, may continue to engage in the business of 
performing electrical work only so long as the responsible representative of such business 
identified on the application for approval of the master electrician business remains an officer of 
such corporation, a partner of such partnership or the proprietor of such sole proprietorship 
unless the department approves a change in the responsible representative as provided in this 
section. The commissioner may promulgate rules providing for the continuation of a master 
electrician business pending the approval of a new responsible representative. 

(iii) Except as otherwise provided in such rules, the revocation, suspension, license 
deactivation or non-renewal of the master electrician's license of the responsible representative 
of a master electrician business automatically revokes its approval to do business and cancels any 
delegation of authority given by such responsible representative to another master electrician 
associated with such business pending the approval by the department of a new responsible 
representative. 

3. Except as otherwise provided by rule, a master electrician business shall not change its name, 
form or designate a new responsible representative without the prior approval of the license board. 
Approval of an application for a change is conditional upon the following: filing the necessary 
forms, payment of the prescribed fee and full payment of all fees incurred with respect to such 
business prior to the date of the change. Except as otherwise provided by rule, a requested change 
shall not be approved if there are any outstanding fees related to the licensee's or master electrician 
business' s professional dealings due and owing to the department or outstanding violation notices 
attributable to the licensee or the master electrician business. 

4. A master electrician's license and a special electrician's license and seal shall not be held by 
any person at the same time. 

5. The holder of a master electrician's license, upon entering employment as a special 
electrician, shall deactivate his or her master electrician's license and seal and change over to a 
special electrician's license and seal to cover the building, buildings, or parts thereof, for which he or 
she will be employed. 

6. Nothing in this chapter shall be construed to prevent two or more master electrician 
businesses from entering into a joint venture of limited duration for a particular project in 
accordance with the rules of the department. An application for a permit involving a joint venture 
shall so indicate on the application and shall identify all of the master electrician businesses that are 
parties to such joint venture by name and authorization number and the names and license numbers 
of the responsible representatives of such businesses. The application shall be signed by the 
responsible representative of one of the parties to the joint venture on behalf of all such parties and 
all of such parties shall be jointly and severally liable for any fees due with respect to electrical work 
performed by such joint venture and for violations of this chapter and the rules of the department 
arising out of such work. 

§27-3013.1 Business establishments, special electricians. 

a. Place of Business, generally. 

1. A special electrician shall at all times have a place of business at a specified address in the city 
at which the licensee may be contacted by the department by mail, telephone or other modes of 



New York City 2011 Electrical Code 1 1 



NYC 2011 Electrical Code Administrative Provisions 



communication. His or her license shall plainly indicate the address or addresses of the building, 
buildings or parts thereof for which such license is issued. 

2. The commissioner may issue more than one special license for a building or buildings if, in 
the commissioner's judgment, he or she deems it necessary for the proper operation and maintenance 
of the electric wiring and equipment of the building or buildings involved. 

b. Insurance. An applicant for approval as a special electrician shall have filed with the commissioner, in 
such form as the commissioner may direct, proof that such applicant's employer carries all insurance 
required by law including, but not limited to, workers' compensation, disability and one million dollars of 
general liability insurance listing the department as certificate holder. Each policy of insurance shall contain 
a provision of continuing liability notwithstanding any recovery under such policy. 

c. Conduct. 

1. A special electrician shall be principally engaged in the business of performing electrical work in or 
on buildings, premises or lots so authorized under the license. 

2. The holder of a special electrician's license shall report in writing any change in employment to the 
license board within thirty days of the change. If such change occurs prior to issuance of the license, an 
applicant shall report the change to the license board within fourteen days of the change. 

3. Applications for permits, and any other document that the commissioner may require to be filed 
with the department, shall bear the stamp of the special electrician's seal as well as the signature of a person 
holding such license. Such person shall personally sign applications for permits and shall have the authority 
to make final determinations and full responsibility for the manner in which the work is done. For 
applications and other documents submitted electronically, the digital signature and imprint of the seal may 
be submitted in a manner authorized by the commissioner. 

§27-3014 Master electrician's and special electrician's licenses and fees. 

a. Before any master electrician's or special electrician's license will be issued or renewed, the 
applicant shall pay a license or renewal fee as prescribed by the department's rules. The commissioner 
may exempt any agency, as defined in chapter fifty-two of the charter, from paying the aforementioned 
fees for licensed special electricians who are employees of such agencies. 

b. Seal. The holder of a master electrician's license shall be issued a seal, of a design or form 
authorized by the commissioner, bearing the holder's full name, license number, and the legend 
"licensed master electrician." The holder of a special electrician's license shall be issued a seal, of a 
design and form authorized by the commissioner, bearing the holder's full name, license number, and 
the legend "licensed special electrician." 

c. No license shall be transferable. The seal is the property of the department and is not transferable 
by the licensee. 

d. The loss or theft of a license or seal must be reported to the department within five calendar days. 
Before any license or seal will be reissued, the applicant shall pay a reissuance fee as prescribed by the 
department's rules. 

e. An application for a change of license from master electrician to special electrician shall involve 
the issuance of a new license and seal with or without examinations as the commissioner may direct. 



1 2 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



f. An application for a change of license from special to master electrician shall be granted only 
upon compliance by the special electrician with all applicable provisions of this chapter and the rules of 
the department. 

g. Each license and seal shall be issued for one year and the full fee shall be payable irrespective of 
the date of issue. 

h. Not more than one license and/or seal shall be issued to an individual and no individual shall 
make or cause to be made a duplicate of such license or seal. 

§27-3015 Renewal of master electrician's and special electrician's licenses. 

a. Any license and seal issued hereunder shall expire one year from the year of issuance on the 
licensee's date of birth for that year irrespective of the date of issue. Such license may be renewed every 
year thereafter without examination, provided application for such renewal, accompanied by the renewal 
fees prescribed above and such information as may be required by the commissioner to ensure 
compliance with section 27-3016 of this chapter and evidence of insurance coverage in compliance with 
section 27-3013 of this chapter, shall have been filed prior to the expiration of the existing license. 

1. Where an applicant can show good and sufficient cause for his or her inability to renew his or 
her license and seal before its expiration, the commissioner may, upon submission of a complete 
application for late renewal within ninety (90) days after the expiration of such license, permit the 
issuance, without examination, of a new license and seal upon payment of the prescribed fees for 
such new license and seal within said ninety days. The commissioner may promulgate rules 
authorizing the renewal of a license up to six months after the expiration of such license for 
extenuating circumstances 

2. No license shall be renewed and no new license and seal shall be issued unless all outstanding 
fees required by section 27-3018 of this code have been paid. 

3. Renewal shall also be subject to the licensee's good moral character. As provided in 
department rule, the licensee's failure to clear open violations in a timely manner may result in the 
refusal to renew a license until the violations are resolved. 

4. The commissioner may promulgate rules requiring applicants for the renewal of master or 
special electrician's licenses to submit proof, in such form as he or she shall determine, that, in each 
year of the license term, such applicant completed at least eight hours of continuing education 
courses approved by the department. Such proof shall be submitted with the license renewal 
application. 

b. If a master electrician's or special electrician's license is suspended for cause, and the restoration 
thereof is conditional upon some action to be taken by the holder of the master electrician's or special 
electrician's license and the holder fails to take action before the expiration of the license, such failure 
shall be cause for the denial of the subsequent application to renew the license and seal. 

§27-3016 Suspension, revocation or deactivation of master electrician's and special electrician's 
licenses and suspension or revocation of approval of master electrician business. 

a. 1. After notice and the opportunity for a hearing in accordance with the rules of the department, 
master electrician's or special electrician's licenses and/or approvals of master electrician businesses 
may be suspended or revoked by the commissioner and/or the commissioner may impose penalties, 
which shall not exceed five thousand dollars for each violation, for violation of this chapter or of any 
of the rules of the department and/or the commissioner may order the licensee to cause the repair of 



New York City 2011 Electrical Code 1 3 



NYC 2011 Electrical Code Administrative Provisions 



electrical damage, and any damage incidental thereto, resulting from any act or omission giving rise 
to a violation as set forth in this chapter or in rules, for any of the following: 

(i) Failure to file an application for a permit or inspection. 

(ii) Failure, upon receipt of a notice of violation, to take the action called for in such notice. 

(iii) Performance of electrical work in a manner contrary to the requirements of the electrical 
code, the electrical code technical standards or other applicable laws and rules enforced by the 
department. 

(iv) Negligence, incompetence, lack of knowledge, or disregard of the code and related laws 
and rules. 

(v) Engaging or assisting in any act that endangers the public safety and welfare. 

(vi) Contract work by holders of special electrician's licenses. 

(vii) Fraudulent dealing or misrepresentation. 

(viii) Conviction of a criminal offense where the underlying act arises out of the individual's 
professional dealings with the city or any other governmental entity 

(ix) False statement in an application for a license or the renewal of a license or in an 
application for approval of a master electrician business or other application or certification 
required by this code or the rules of the commissioner, or in any proof or instrument in writing in 
connection therewith. 

(x) The making of a material false or misleading statement on any form or report filed with 
the department or other governmental entity. 

(xi) The failure to file a statement, report or form required by law to be filed. 

(xii) Willfully impeding or obstructing the filing of a statement, report or form of another 
required by law to be filed. 

(xiii) Poor moral character that adversely reflects on the licensee's fitness to conduct work 
regulated by this code. 

(xiv) Failure to pay outstanding fees owed pursuant to section 27-3018 of this chapter. 

(xv) Failure to comply with this code or any order, rule, or requirement lawfully made by the 
commissioner including failure to cooperate with investigations related to the electrical field 
conducted by the commissioner or other government entity. 

(xvi) Failure to provide documents, including payroll records, workers' compensation or 
other insurance documents, employee timekeeping records and corporate tax returns, required or 
requested by the commissioner. 

2. Notwithstanding any inconsistent provision of paragraph one of this subdivision if, after due 
inspection, the commissioner determines that a licensee and/or a master electrician business has 
performed electrical work which is not in compliance with the electrical code, the electrical code 
technical standards, or any other laws or rules enforced by the department, and which has resulted in 
a condition severely hazardous to life or property, the commissioner may suspend his or her license 
and/or the authorization of a master electrician business represented by such licensee without a prior 
hearing. Notice of such suspension shall be served on the licensee and/or the master electrician 



14 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



business. The commissioner shall provide the licensee and/or the master electrician business with 
the opportunity for a hearing within five (5) calendar days after such suspension. 

b. In the event the holder of a master electrician's license is no longer engaged in a master electrician 
business or a special electrician is engaged during normal working hours in a business activity that does 
not involve the installation, alteration, or repair of electrical wiring for light, heat or power, then he or 
she shall so notify the department and submit his or her license and seal for deactivation provided that (i) 
such license and seal will be reinstated without examination if such application is made prior to the date 
on which it would have otherwise expired, or (ii) if application is made after such date a new license and 
seal will be issued, without written re-examination, after the submission of satisfactory evidence of 
continued competence in the electrical field and satisfaction of any applicable continuing education 
requirements during the period of deactivation; provided that at the time of the submission of the license 
for deactivation. 

1. All outstanding fees required by section 27-3018 of this chapter are paid, and 

2. There are no outstanding violation notices for electrical work performed under such license, and 

3. Open applications filed under such license have been scheduled for inspection in accordance 
with department procedures, re-filed by another licensee or have been withdrawn. 

c. During the period of deactivation, the licensee must continue to pay the license renewal fee 
required by this chapter for each year of the deactivation period. 

d. During any period of deactivation, or upon the suspension or revocation, of a master electrician's 
or special electrician's license, the holder shall surrender his or her seal to the department. Upon the 
death of a holder, his or her seal shall be immediately surrendered to the department. 

e. The fees required for the reinstatement of a license after deactivation or suspension shall be the 
same as those required to obtain the license. 

f. If reinstatement of the license is not requested within thirty days of the expiration of a suspension, 
late fees shall be imposed as prescribed by the department's rules. 

§27-3016.1 Certification as low voltage installer; qualifications; issuance; fees. 

a. An individual who has been determined by the commissioner to be competent to perform low 
voltage electrical work in compliance with the electrical code and the electrical code technical standards, 
the building code and other applicable law and who otherwise qualifies in accordance with this section 
and the rules of the department may be certified as a low voltage installer. 

b. An applicant for such certification shall be over the age of eighteen years, of good moral character 
and at the time of application shall have had two (2) years of satisfactory experience as set forth in the 
rules of the department. 

c. Every such application shall be made in writing in such form and shall furnish such information 
as the commissioner shall prescribe and set forth in the rules of the department. Every applicant shall 
submit to an investigation to determine the applicant's character and fitness. 

d. Such certification shall be issued for such term and shall be subject to renewal in accordance with 
such conditions as shall be prescribed in the rules of the department. 

e. The fee for such certification and for the renewal thereof shall be prescribed by rule. 



New York City 2011 Electrical Code 1 5 



NYC 2011 Electrical Code Administrative Provisions 



f. Certification as a low voltage installer may be suspended or revoked for cause in accordance with 
the rules of the department and/or the department may impose penalties which shall not exceed one 
thousand dollars for each violation for violations of this chapter, the electrical code, the electrical code 
technical standards or the rules of the department. 

§27-3017 Electrical work by unauthorized persons; false representations. 

a. Work without appropriate license, false representation prohibited. 

1. Except as otherwise provided in paragraph two of this subdivision, it shall be unlawful for any 
person to perform electrical work except under a license issued to a master electrician or special 
electrician as provided in this chapter. It shall be unlawful for any person to advertise or to hold 
himself, herself or itself out as authorized to engage in the business of performing electrical work 
unless such person is authorized to perform such work pursuant to this chapter under an appropriate 
master electrician's or special electrician's license. No person shall cause any such work to be done 
by any person unless he or she is an employee of and working under the direct supervision of a 
person authorized to perform such work pursuant to this chapter and the rules of the department. No 
person shall falsely represent that he, she or it is authorized to perform electrical work under a 
master electrician's or special electrician's license or shall use in any advertising the words "master 
electrician" or the words "licensed electrician" or the words "electrical contractor" or any words of 
similar meaning or import on any sign, card, letterhead or in any other manner unless such person is 
so authorized pursuant to this chapter and the rules of the department. 

2. Notwithstanding any inconsistent provision of paragraph one of this subdivision, the 
commissioner may authorize business entities engaged in the business of installing, maintaining or 
repairing communication, signaling, alarm or data transmission systems to perform low voltage 
electrical work under a certification issued to a low voltage installer as provided in this chapter and 
the rules of the department. 

b. False statement. No person shall, with intent to defraud or deceive, knowingly make a false 
statement, or cause or procure to be made or aid and assist in the making of a false statement in an 
application for a master electrician's or special electrician's license or for certification as a low voltage 
installer or in an application for approval of a master electrician business or the renewal of a license or 
certificate or in an application for a permit and approval or in any application provided for in this 
chapter, or in any proof or instrument in writing in connection therewith, or in any examination 
hereunder, deceive or substitute or cause another to deceive or substitute. 

c. Penalty. Any person, partnership or corporation who shall violate any of the provisions of this 
section shall be guilty of a misdemeanor punishable by a fine of not less than five hundred dollars nor 
more than five thousand dollars for the first offense, not less than one thousand dollars nor more than 
five thousand dollars for the second offense, and not less than fifteen hundred dollars nor more than five 
thousand dollars for the third offense or any successive offense thereafter or by six months 
imprisonment or by both such fine and imprisonment. 



1 6 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



827-3017.1 Cooperation required. 

authorized by law, including but not limited to suspension or revocation of the license. 

the date and time specified therein. 

827-3018 Inspection; application for permit and application fees. 

a The commissioner or any officer or employee of the department authorized thereto b the 

thirty days, or both. , , 

b Before commencing any electrical work, other than low voltage electrical work a master 



years 



fS ' 1 Permits shall be deemed to incorporate the provisions that the applicant the owner, and then 

permitted or authorized. 

? All work shall conform to the approved submittal documents and any approved amendments 

therL^ 

* Th P nermit shall expire by operation of law if the insurance required pursuant to Section 27- 
301 'M^-^^ the permit was conditioned, lapses, expires or is cancelled, 
unless the permit holder files proof of valid insurance before such event. 

c Fees. The fee for a permit for minor electrical work as described in subdivision h of this section 
shall be fifteen dollars, payable upon filing of the application. 



New York City 2011 Electrical Code 



17 



NYC 2011 Electrical Code Administrative Provisions 



1. An initial application fee for electrical work requiring a permit shall be payable as follows- 
forty dollars upon filing of the application for such work. 

nr ?• l he balance of Ae application fee shall be payable at electrical sign-off from the department 
or as otherwise provided by the department's rules. 

fwi« ' I 1 *, f r,f r electric ^ work re 1 uirin g a work permit by the department shall be computed as 
follows but shall not exceed five thousand dollars : 

(i) Each outlet, each fixture, each horsepower or fraction thereof of a motor or generator 
each kilowatt or fraction thereof of a heater, each horsepower or fraction thereof of an air 
conditioner each kilovolt-ampere or fraction thereof of a transformer installed, altered or 
repaired shall be assigned the value of one unit. In computing the aforementioned fee, the sum 
ot toe units will determine the charges as set forth herein below: 

Sum of units „ 

, 7Z Fee 

'- ,0 $0M 

Over 10 * no , 

3>0.25 per unit 

(n) For each service switch installed, altered or repaired: 

0-100 Amperes \ $ g QQ 

101-200 Amperes $3Q 00 

201-600 Amperes $105 00 

601-1200 Amperes $225 00 

Over 1200 Amperes j 375 QQ 

alter^o/repaTred: 86 ' ^ ^^ ^^ ^ "* fw '^ '^'of 'fe^te'^uctois installed, 
Up to #2 Conductors $]5 0f) 

Over #2 to #1/0 Conductors ..".' $30 00 

Over #1/0 to 250 MCM $4 ' 00 

Over 250 MCM il'l'!l'll'!!"!!!Z!Z.'.'.'.'".".'.'.'."'$75'oO 

(iv) For each panel installed, altered or repaired: 

1 Phase up to 20-1 or 10-2 pole cutouts or breakers $15 

1 Phase over 20-1 or 10-2 pole cutouts or breakers ...........$37 50 

3 Phase up to 225 amperes $50 00 

3 Phase over 225 amperes $75 00 

(v) (a) For each sign manufactured (in-shop inspections): .".........."$40 00 

(b) For each sign manufactured (on-site inspections)- 

to 30 square feet $65 00 

31 to 60 square feet $9Q 0Q 

Over 60 square feet $1 15 

(vi) For each elevator: 

10 floors or less $ 

Each additional ten or fewer floors $83 00 



(vii) For wiring or rewiring boiler controls in buildings: Z" $12 



00 



18 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



d. If, after inspection, such wiring or appliances shall be found to have been installed, altered or 
repaired in conformity with the requirements of this chapter, the electrical code, the electrical code 
technical standards and the rules of the department, and the required fees paid, the commissioner shall 
issue to the applicant a sign-off of the approved work completed. The provisions of this subdivision 
shall not apply to work performed pursuant to a permit for minor electrical work as defined in 
subdivision h of this section. 

e. Whenever a master electrician business or special electrician files an application for a permit 
covering electrical work installed by an unlicensed or unauthorized person, it shall be his or her duty to 
specify such fact upon the application. 

f. The commissioner shall be entitled to charge special fees. 

1. For an application with respect to electrical work made after a violation was issued for failure 
to file an application for a permit for such work - up to ten times the total fee that would otherwise 
be payable as set forth in subdivisions c and d of this section. 

2. Duplicate copy of notice of violation - $5.00. 

g. No application or fees shall be required for electrical work relating to the construction and 
maintenance of city street lights and city traffic lights owned, operated or controlled by the city 
government or any agency thereof. 

h. 1 . For purposes of this section a permit for minor electrical work may be issued for any of the following: 

(i) replacement of defective circuit breakers or switches rated thirty amperes or less, 
excluding main service disconnects; 

(ii) replacement of parts in electrical panels where voltage does not exceed one hundred fifty 
volts to ground; 

(iii) replacement of minor elevator parts as defined by rule; 

(iv) replacement of defective controls rated at thirty amperes or less; 

(v) repair of defective fixtures; 

(vi) replacement of fixtures in existing outlets, provided the number of such fixtures does not 
exceed five and does not increase existing wattage; 

(vii) replacement, repair, disconnection or reconnection of motors not to exceed one 
horsepower, and associated devices; 

(viii) repairs to low pressure heating plants with a capacity of less than fifteen pounds per 
square inch, except as may otherwise be required by rule of the commissioner. 

(ix) installation of any ten or fewer units not requiring the installation of an additional 
branch circuit; 

(x) installation of motors of fractional horsepower; 

(xi) installation of transformers rated at one thousand volt amperes or less. 

2. Notwithstanding any other provision of this chapter, an electrical sign-off by the department 
shall not be required for electrical work performed pursuant to a permit for minor electrical work. 



New York City 2011 Electrical Code 19 



NYC 2011 Electrical Code Administrative Provisions 



3. Notwithstanding any other provision of this chapter, the commissioner may promulgate a rule 
providing that minor electrical work may be performed without a permit or the payment of a fee 
under the conditions to be prescribed in such rule. 

i. The department shall not issue a permit or, if applicable, an electrical sign-off pursuant to an 
application that involves the energizing of a meter in a one-, two-, three-, or four-family residence, if the 
department finds that such action will cause the total number of meters for the building to exceed the 
number of dwelling units specified for such building in the certificate of occupancy, or if there is no 
certificate of occupancy, as determined by the department, except as permitted herein. A building 
specified as a one-family residence in the certificate of occupancy or, if there is no certificate of 
occupancy, as determined by the department, may have only one electric meter. A building in which 
two or more dwelling units have been constructed in accordance with the certificate of occupancy, or if 
there is no certificate of occupancy, as determined by the department, may have one meter for each 
dwelling unit and one additional meter for the common areas of the building, provided that smoke 
detecting devices are installed in all common areas in accordance with departmental requirements. Such 
common areas may include boiler rooms, shared hallway lighting, shared stairway lighting, and outdoor 
perimeter lighting but shall not include any habitable space. In the event that a meter has been found to 
have been installed or to exist in violation of this section, the department may take action leading to the 
disconnecting of such meter in accordance with the notice requirements set forth in section 27-3020 of 
this chapter. 

j. Any application for a permit filed with the department in relation to a request for the authorization 
to power or energize/electrical wiring or appliances or power generating equipment or in relation to 
work that will result in the issuance of a new or amended certificate of occupancy must include a 
statement, signed and sealed by the electrician, that the building owner or his or her authorized 
representative has authorized in writing the work to be performed. This signed authorization must be 
available upon request by the department. In addition, any electrical application filed with the 
department involving the energizing of a meter, must include as well, a statement, signed and sealed by 
the electrician, that the building owner or his or her authorized representative has indicating in writing 
the intended use or purpose of such meter and has affirmed that such meter will be maintained in 
compliance with the provisions of this section. This statement must be available upon request by the 
department. 

k. Any authorization to power or energize electrical wiring or appliances issued by the department 
shall expire ninety days after the date of issuance unless a sign-off has been issued by the department or 
an extension of such authorization has been granted by the department. In the event no such sign-off has 
been issued or extension authorization granted, the department may take action leading to the 
disconnecting of such meter(s) in accordance with the notice requirements set forth in section 27-3020 
of this chapter. 

1. Any permit application filed with the department that requires the selective coordination of overcurrent 
protective devices must include documentation from a professional engineer demonstrating how selective 
coordination was achieved, including but not limited to short circuit overlay curves and calculations. Such 
documentation shall be submitted to the department prior to sign off. 

m. For permit applications requiring compliance with the applicable energy conservation code, 
documentation demonstrating compliance must be available upon request by the department. 

n. The provisions of this section shall not apply to low voltage electrical work. 



20 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



o. An application for a work permit may be amended by filing with the department a post-approval 
amendment in a form prescribed by rule of the department. 

§27-3019 Modification, suspension or revocation, electrical sign-off, permit or other authorization. 

a. The commissioner may at any time by an order in writing for good cause shown, modify, suspend 
or revoke any sign-off, permit or other authorization issued pursuant to this chapter for failure to comply 
with the provisions of this code or other applicable laws or rules; or whenever there has been any false 
statement or any misrepresentation as to a material fact in the application or submittal documents upon 
the basis of which such approval was issued; or whenever a permit has been issued in error and 
conditions are such that the permit should not have been issued. Such notice shall inform the permit 
holder of the reasons for the proposed action and that the applicant has the right to present to the 
commissioner or his or her representative within ten business days of delivery of the notice by hand or 
fifteen calendar days of the posting of notice by mail, information as to why the permit should not be 
modified, suspended or revoked. A copy of any such order shall be served in the manner provided in 
this subchapter. No person other than the commissioner or an officer or employee of the department, 
duly authorized thereto by the commissioner, shall alter or amend any sign-off, permit or other 
authorization issued pursuant to this chapter or the rules of the department. 

b. Immediate suspension in cases of imminent peril. The commissioner may immediately suspend 
any permit without prior notice to the permit holder when the commissioner has determined that an 
imminent peril to life or property exists. The commissioner shall immediately notify the permit holder 
that the permit has been suspended and the reasons therefore, that it is proposed to be revoked, and that 
the permit holder has the right to present to the commissioner or his or her representative within 10 
business days of delivery of the notice by hand or 15 calendar days of the posting of notice by mail 
information as to why the permit should not be revoked. 

§27-3020 Supplying or discontinuing electrical energy. 

a. Except as otherwise provided in this code, no person, partnership or corporation shall supply, or 
cause to be supplied or used, electrical energy for light, heat or power, signaling, alarm or data 
transmission to any wiring or appliance in any building unless a sign-off or other authorization as set 
forth in the rules of the department authorizing the use of said wiring or appliance shall have been issued 
by the commissioner. 

b. If, in the judgment of the commissioner, after due inspection, the continued use of any electric 
wiring or appliances in or on any building or structure shall be unsafe or dangerous to persons or 
property, the commissioner may cause such wires or appliances to be disconnected from the supply of 
electrical energy and to seal the wiring and appliances so disconnected. Thereafter, no person shall 
cause or permit electrical energy to be supplied to the wiring or appliances so sealed until the same shall 
have been made safe and the commissioner shall have issued a certificate to that effect; provided, 
however, that no wiring or appliances shall be disconnected pursuant to this section until a notice in 
writing, stating specifically the reason why such wiring or appliances must be disconnected, shall have 
been served, as provided in this chapter, and a duplicate thereof shall have been delivered to the person 
supplying the electrical energy to such wiring or appliances. 

§27-3021 Service of orders and notices. Any order or notice issued pursuant to the provisions of this 
chapter may be served personally upon the person, partnership or corporation to whom or to which it is 
addressed, or may be served by mailing the same in a sealed envelope with postage prepaid, directed, in 
the case of the holder of any license, to the address furnished by such license holder to the department of 



New York City 2011 Electrical Code 21 



NYC 2011 Electrical Code Administrative Provisions 



buildings as his or her business address, or the address of the master electrician business represented by 
the licensee and, in the case of any other person, partnership or corporation, to the premises where the 
defects recited in such order are alleged to exist and by the posting in a conspicuous place on such 
premises of a copy of such notice or order. The service as above described, by mailing and posting, 
shall be the equivalent of personal service. 

§27-3021.1 Electric meter installation; restriction. No public utility shall supply electricity to a one, 
two, three or four family residence building, nor shall such utility energize more electrical meters in a 
building than the number of distinct and separate residences in such building as authorized in the 
certificate of occupancy applicable thereto, or if there is no certificate of occupancy, as determined by 
the department, without first receiving a sign-off from the department. In the event that an owner of a 
one, two, three or four family building wants to install an additional electrical meter other than provided 
for herein, approval shall be obtained in writing from the department. A public utility shall not install 
such additional electrical meter without such approval. A building in which two or more dwelling units 
have been constructed in accordance with the certificate of occupancy, or if there is no certificate of 
occupancy, as determined by the department, may have one meter for each dwelling unit and one 
additional meter for the common areas of the building, provided that smoke detecting devices are 
installed in all common areas in accordance with departmental requirements. Such common areas may 
include boiler rooms, shared hallway lighting, shared stairway lighting, and outdoor perimeter lighting 
but shall not include any habitable space. In the event that a meter has been found to have been installed 
or to exist in violation of this section, the utility must report such findings to the department, which may 
take action leading to the disconnecting of such meter in accordance with the notice requirements set 
forth in section 27-3020 of this code. 

§27-3021.2 Violations. Except as otherwise provided in this chapter, any person or business who shall 
violate any of the provisions of this chapter or who shall fail to comply with any requirement thereof or 
with the electrical code technical standards or who shall violate or fail to comply with any order or rule 
of the commissioner made thereunder shall, for each and every violation or noncompliance be subject to 
penalties and other enforcement actions in accordance with the provisions of chapter 2 of title 28 of the 
administrative code. 

§27-3024 Adoption of the electrical code technical standards. 

a. The city of New York hereby adopts the 2008 edition of the National Fire Protection Association 
NFPA 70 National Electrical Code as the minimum requirements for the design, installation, alteration 
or repair of electric wires and wiring apparatus and other appliances used or to be used for the 
transmission of electricity for electric light, heat, power, signaling, communication, alarm and data 
transmission in the city subject to the amendments adopted by local law and set forth in section 27-3025 
of this subchapter, which shall be known and cited as " the New York city amendments to the 2008 
National Electrical Code." Such 2008 edition of the National Fire Protection Association NFPA 70 
National Electrical Code with such New York city amendments shall together be known and cited as the 
"electrical code technical standards." The commissioner shall make a copy of the electrical code 
technical standards available for public inspection at the department of buildings. 

b. No later than August thirty-first, two thousand twelve and on or before such date in every third 
year thereafter, the commissioner shall submit to the city council proposed amendments that he or she 
determines should be made to the electrical code technical standards to bring them up to date with the 
latest edition of the National Fire Protection Association NFPA 70 National Electrical Code or otherwise 
modify the provisions thereof. In addition, prior to the submission of such proposal to the city council, 



22 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Administrative Provisions 



such proposal shall be submitted to an advisory committee established by the commissioner pursuant to 
this chapter for review and comment. 

§ 27-3025 The New York City Amendments to the 2008 National Electrical Code. The following 
New York City amendments to the 2008 National Electrical Code are hereby adopted as set forth in this 
section. In the event of conflicts between technical provisions, the more restrictive shall apply. 
Technical provisions commence on page 25. 



New York City 2011 Electrical Code 23 



Section 90.2 through Section 110.34 NYC 2011 Electrical Code Technical Provisions 



24 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 90.2 through Section 110.34 

ARTICLE 90 
Introduction 



SECTION 90.2 

Subsection 90.2(B)(5) - Delete paragraph (b) and add a new paragraph (b) to read as follows: 

(b) Are located in legally established easements, rights-of-way, or by other agreements either 
designated by or recognized by public service commissions, utility commissions, or other regulatory 
agencies having jurisdiction for such installations, or 



Chapter 1 
General 
ARTICLE 100 
Definitions 

Coordination (Selective). Add a new sentence at the end of the definition of Coordination (Selective) 
to read as follows: 

For the purposes of this code two overcurrent protective devices shall be deemed selectively coordinated 

if their respective time-current characteristic curves do not intersect at a time of 0.1 seconds (6 cycles on 

60 Hz systems) or longer. 

Electric Closet. Add a new definition of Electric Closet immediately after "Dwelling Unit," to read as 

follows: 

Electric Closet. A room designed for or dedicated to the purpose of containing electrical distribution 

equipment such as vertical risers, bus ducts, transformers or panelboards. 



ARTICLE 110 

Requirements for Electrical Installations 

SECTION 110.2 

Section 1 10.2 - Delete in its entirety and add a new section 1 10.2 to read as follows: 

110.2 Approval of Electrical Materials, Equipment and Installations. 

(A) Listed and Approved Materials and Equipment. All electrical equipment, apparatus, materials, 

devices, appliances or wiring thereto installed or used in any electrical construction or installation 

regulated by the terms of this code, shall be designed and constructed so as to be safe and suitable for 

the purpose intended. 



New York City 2011 Electrical Code 25 



Section 90.2 through Section 110.34 NYC 2011 Electrical Code Technical Provisions 

(1) All electrical equipment, apparatus, materials, devices, appliances and wiring used in New York City shall 
be approved by the commissioner, with submissions required in accordance with rules of the department. 

(2) The maker's name, trademark or other identification, symbol and number shall be placed on fittings, 
equipment and materials. Additional markings shall be provided, stating voltage, current, wattage or 
other appropriate ratings as prescribed elsewhere in this code. 

(B) Installations. All electrical installations regulated by the terms of this code shall be designed and 
constructed so as to be safe and suitable for the purpose intended. 

No electrical installations as described in (1) through (5) below shall be constructed unless a submission 
for approval has been made to the commissioner and approval has been granted. For the purpose of this 
section an electrical "installation" shall refer to the installation of service equipment, transformers, UPS 
systems, generators, electrical wiring of assembled photovoltaic arrays, generator paralleling equipment 
or other sources. 

(1) A new installation of new equipment totaling 1000 kVA or larger. 

(2) Any change in an installation with a rating of 1000 kVA or larger, up to and including 2nd level overcurrent 
protection unless it was folly described and approved as "future" on the original approved plan. 

(3) Any addition to an existing installation, which would bring the total to 1000 kVA or larger. 

(4) The addition of any equipment in a room, which would affect clearances around the equipment of a 
1000 kVA installation. 

(5) A new installation or revised installation above 600V irrespective of kVA rating. 

Exception No, 1: No submission is required solely for fire alarm service taps. 

Exception No. 2: No submission is required for the addition of one 2nd level overcurrent protection 
device 200 amperes or less, 

(C) Capacity. 

(1) The capacity of a utility service, in kVA, shall be determined by summing the maximum ampere 
ratings of each service disconnecting means and calculating total kVA at the operating voltage. Service 
disconnecting means supplying fire pumps shall be included at 125 percent of the fire pump full load 
amps. The calculation shall include all new and existing service disconnecting means supplied from the 
common service entrance. 

(2) The capacity of a transformer, UPS system, generator or other source shall be its maximum kVA 
output rating. 

FPN: See 90.7, Examination of Equipment for Safety, and 110.3, Examination, Identification, 
Installation, and Use of Equipment. See definitions of "Approved," "Identified," "Labeled," and "Listed." 

SECTION 110.4 

Section 1 10.4 - Add a FPN at the end of the section to read as follows: 

FPN: See Section 27-3004 of the Administrative Code for the definitions of Low Voltage 
Electrical Work and Low Voltage Installer, and Section 27-3016.1 for the certification 
requirements of a Low Voltage Installer. 



26 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Techn ical Provisions Section 90.2 through Section 110.34 

SECTION 110.25 

Section 1 10.25 - Add a new section 1 10.25 to read as follows: 

110.25 Electric Closets. Electric closets shall be dedicated to electrical distribution equipment. Electric 

closets shall be identified as such, shall be sized to provide the applicable working space requirements, 

and shall not be used for any other purpose including storage. Electric closets shall be accessible to 

authorized persons only. 

Exception: Other systems that are required to he installed by a licensed electrician, such as Fire Alarm 

Panels, Building Management Systems and Lighting Control Systems may be installed in Electric Closets. 

SECTION 110.26 

Subsection 1 10.26(H) - Add a new subsection 1 10.26(H) to read as follows: 

(ID Network Compartments. All network compartments shall have at least two means of access. 

Each door shall access an area that leads to a legal exit. 

SECTION 110.31 

Section 1 10.31 - Revise the second sentence of the second paragraph to read as follows: 

A fence shall not be less than 2.44m (8 ft) in height. 

Subsection 1 10.31(A) - Revise the second sentence to read as follows: 

The floors of vaults in contact with the earth shall be of concrete that is not less than 6 in. (150 mm) 

thick, but where the vault is constructed with a vacant space or other stories below it, the floor shall have 

adequate structural strength for the load imposed on it and a minimum fire resistance of 3 hours. 

SECTION 110.33 

Subsection 1 10.33(A) - Revise the first sentence of the subsection to read as follows: 
At least one entrance to enclosures for electrical installations as described in 110.31 not less than 762 
mm (30 in.) wide and 2 m (6% ft) high shall be provided to give access to the working space around the 
electrical equipment. 

SECTION 110.34 

Subsection 1 10.34(A) - Revise the last sentence of the Exception to read as follows: 

Where rear access is required to work on de-energized parts on the back of enclosed equipment, a 

minimum working space of 900 mm (36 in.) horizontally shall be provided. 



New York City 2011 Electrical Code 



27 



Section 210.11 through Section 285.25 NYC 2011 Electrical Code Technical Provisions 



28 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Techni cal Provisions Section 210.11 through Section 285.25 

Chapter 2 

Wiring and Protection 

ARTICLE 210 
Branch Circuits 

SECTION 210.11 

Subsection 210.1 1(C)(4) - Add a new subsection 210.1 1(C)(4) to read as follows: 
(4) Air-Conditioning Branch Circuit. In addition to the number of branch circuits required by other 
parts of this section, an individual branch circuit shall be provided for each air-conditioning receptacle 
required by 210.52(1). 

SECTION 210.19 

Subsection 210.19(A)(1) - Add a new sentence at the end of the paragraph before the first Exception to 
read as follows: 

Conductors of branch circuits shall be sized to allow for a maximum voltage drop of 3 percent at the last 
outlet supplying light, heat or power and the maximum voltage drop allowable for feeders and branch 
circuit combined shall not exceed 5 percent. 

FPN No. 4 - Delete the FPN in its entirety. 
Subsection 210.19(A)(4) - Revise the first sentence of the paragraph by replacing "14 AWG" with "12 
AWG" 

Exception No. 3: Add a new Exception No. 3 to read as follows: 

Exception No. 3: Where compliance with the applicable Energy Conservation Code is mandated voltage 
drop requirements of that code shall apply. 

SECTION 210.24 

Section 210.24 Table - Replace the value "14" that appears twice in the column headed 15 A, and once 
each in the columns headed 20A and 30A in the Circuit Rating Section with the value "12." 

SECTION 210.25 

Section 210.25 - Add an Exception to (A) and (B) to read as follows: 

Exception to (A) and (B): Buildings built prior to January 1, 2003 are exempt from the requirements of 

210.25 (A) and (B) under either of the following conditions: 

(1) undergoing renovation less than 50 percent. 

(2) repair to or replacement of existing equipment. 



New York City 2011 Electrical Code 



29 



Section 210.11 through Section 285.25 NYC 20 11 Electrical Code Technical Provisions 

SECTION 210.52 

Subsection 210.52(E)(3) - Delete the Exception in its entirety. 

Subsection 210.52(1) - Add a new subsection 210.52(1) to read as follows: 

(I) Outlet Requiremen ts For Residential-Type Occupancies. In addition to the requirements set forth 
in subsections (A) through (H) of this section, living rooms, bedrooms, dining rooms or similar rooms 
shall have at least one receptacle outlet installed for air conditioners. Such outlets shall be supplied by an 
individual branch circuit. 

Exception: Buildings with central air conditioning systems that serve any of the above areas shall not 
require separate outlets in those areas. 



ARTICLE 215 
Feeders 

SECTION 215.2 

Subsection 215.2(A)(1) - Add two new sentences at the end of the first paragraph, before the Exception, 
to read as follows: 

Feeder conductors shall be sized so that the maximum voltage drop at the last overcurrent device does 
not exceed 3 percent and the total maximum voltage drop of feeder and branch circuit conductors to the 
last outlet does not exceed 5 percent. The minimum feeder size feeding a dwelling unit shall be 8 AWG 
copper or 6 AWG aluminum or copper-clad aluminum conductors. 

Add three new Exceptions No. 3, No. 4 & No. 5 and a FPN, to read as follows: 

Exception No. 3: For residential occupancies and portions of the electrical system of mixed use 
buildings serving exclusively residential occupancies, the maximum voltage drop from the service point 
to the last overcurrent device shall not exceed 4 percent and the total maximum voltage drop to the last 
outlet shall not exceed 5 percent. 

Exception No. 4: Where the distance between the utility service point and the service disconnecting 
means exceeds 15.2 m (5 Oft), the voltage drop between the service point and the service disconnecting 
means may be calculated utilizing the service capacity limits defined by the utility company in lieu of the 
computed load. The distance between the service point and the service disconnecting means, the 
computed load and a letter on utility company letterhead indicating service limits shall be submitted for 
department approval. 

Exception No. 5: Where compliance with the applicable Energy Conservation Code is mandated voltage 
drop requirements of that code shall apply. 

FPN: When using Exception No. 4, potential future increases in the utility service capacity limits 
should be considered to avoid exceeding voltage drop limits at a later date. 

Subsection 215.2(A)(3) - Delete FPN No. 2. - Renumber FPN No.3 as FPN No.2, and revise to read as 
follows: 

FPN No. 2: See amended 210.19(A) for voltage drop on branch circuits. 



30 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Pr ovisions Section 210.11 through Section 285.25 

ARTICLE 220 

Branch-Circuit, Feeder, and Service Calculations 

SECTION 220.14 

Section 220.14 - Delete the reference to subdivision (L) in the first paragraph and replace it with a 

reference to subdivision (M) to read as follows: 

In all occupancies, the minimum load for each outlet for general-use receptacles and outlets not used for 

general illumination shall not be less than that calculated in 220.14(A) through (M), the loads shown 

being based on nominal branch-circuit voltages. 

Subsection 220.14(M) - Add a new subsection 220.14(M) to read as follows: 

flVT) Air Conditioning Circuits. A load of not less than 1500VA shall be included with each 2 wire 

circuit. This load shall be permitted to be included with the general lighting load and subject to section 

220.42 and table 220.42. 

SECTION 220.87 

220.87 Determining Existing Loads. 

Delete "or service" from the first sentence. 

ARTICLE 225 

Outside Branch Circuits and Feeders 



SECTION 225.10 

Section 225.10 - Revise the first sentence to read as follows: 

The installation of outside wiring on surfaces of buildings shall be permitted for circuits of not over 600 
Volts, nominal, as multiconductor cable, as type MI cable, as messenger supported wiring, in rigid metal 
conduit, in intermediate metal conduit, in cable trays, as cablebus, in wireways, in auxiliary gutters, in 
liquidtight flexible metal conduit and in busways. 

SECTION 225.11 

Section 225.1 1 - Revise the first sentence to read as follows: 

Where outside branch and feeder circuits leave or enter a building, the requirements of 230.54 shall apply. 



New York City 2011 Electrical Code 



31 



Section 210.11 through Section 285.25 NYC 2011 E lectrical Code Technical Provisions 

SECTION 225.36 

Section 225.36 - At the end of the sentence, add the following: 

and shall comply with all the requirements of Article 408 and its amendments. 

ARTICLE 230 

Services 

SECTION 230.615^ 

Subsection 230.6(5) - Add a new subsection 230.6(5) to read as follows: 

(5) Where installed in service and fire pump rooms having 2 hour rated construction. 

SECTION 230.30 

Section 230.30 - Delete the Exception in its entirety. 

SECTION 230.31 

Subsection 230.31(B) - Revise to read as follows: 

(B) Minimum Size. The conductors shall not be smaller than 4 AWG copper or 2 AWG aluminum or 
copper-clad aluminum. 

Exception: Conductors supplying only limited loads of a single branch circuit — such as small 
polyphase power, controlled water heaters, and similar loads — shall not be smaller than 10 AWG 
copper or 8 A WG aluminum or copper-clad aluminum. 

SECTION 230.42 

Subsection 230.42(A) - Revise to read as follows: 

(A) General. The ampacity of the service-entrance conductors before the application of any adjustment or 
correction factors shall not be less than (A)(1) or (A)(2) below. Loads shall be determined in accordance with 
Part III, IV or V of Article 220, as applicable. Ampacity shall be determined from 310.15 for respective 
conductor types at 75°C. When service-entrance conductors consist of busbars contained in either service 
busway or other service equipment, bus sizing shall conform to the following table: 

Table 230.42 Service Equipment Busbar Ampere Density 

Maximum Current Per Square Inch in Amperes 
Current Rating Ventilated Housing Unventilated Housing 

ofBus Copper Bar Aluminum Bar Copper Bar Aluminum Bar 

Up to 1200 Amp 1000 750 800 600 

1201 to 2000 Amp 800 600 700 525 

2001 Amp and greater 700 525 500 375 



32 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technica l Provisions Section 210.11 through Section 285.25 

(1) Ampacity of the service-entrance conductors for service below 1000 kVA shall not be less than 
either a or b: 

(a) The sum of the noncontinuous loads plus 125 percent of the continuous loads. 

(b) The sum of the noncontinuous loads plus the continuous loads if the service-entrance 
conductors terminate in an overcurrent device where both the overcurrent device and its 
assembly are listed for operation at 100 percent of their rating. 

(2) Ampacity of the service-entrance conductors for services 1000 kVA and larger shall not be less than 
the sum of the maximum ampere ratings of the service disconnecting means. When including fire pump 
disconnects in the calculation, 125 percent of the fire pump full load amperes shall be added. 
Exception: The ampacity of service-entrance conductors need not exceed the maximum demand 
calculated in accordance with Article 220, up to a maximum of 4000 amps per service 

FPN: See Subsection 110.2(C)(1) for determining service capacity. 

SECTION 230.43 

Section 230.43 - Revise to read as follows: 

230.43 Wiring Methods for 600 Volts, Nominal, or Less. Service-entrance conductors shall be 
installed in accordance with the applicable requirements of this Code covering the type of wiring 
method used and shall be limited to the following methods: 

(1) Type IGS cable. 

(2) Rigid metal conduit. 

(3) Intermediate metal conduit. 

(4) Electrical metallic tubing. 

(5) Metallic wireways. 

(6) Busways. 

(7) Metallic auxiliary gutters. 

(8) Rigid nonmetallic conduit, underground. 

(9) Mineral-insulated, metal-sheathed cable. 

(10) Flexible metal conduit not over 1.83 m (6 ft) long or liquidtight flexible metal conduit not over 1.83 
m (6 ft) long between raceways, or between raceway and service equipment, with equipment bonding 
jumper routed with the flexible metal conduit or the liquidtight flexible metal conduit according to the 
provisions of Section 250.102(A), (B), (C), and (E). 

Service entrance conductors shall not run within the hollow spaces of frame buildings. 



New York City 2011 Electrical Code 



33 



Section 210.11 through Section 285.25 NYC 2011 Electrical Code Technical Pr ovisions 

SECTION 230.46 

Section 230.46 - Revise to read as follows: 

230.46 Unspliced Conductors. Service-entrance conductors shall not be spliced before terminating at 
the service disconnecting means, except for the following terminations that are permitted: 

(1) in a service end line box. 

(2) taps supplying two to six service disconnecting means when grouped. 

(3) approved terminals in meter enclosures. 

(4) service-entrance conductors in the form of busway, shall be connected as required in order to 
assemble the various fittings and sections. 

SECTION 230.50 

Subsection 230.50(B)(1)(3) - Delete the subsection in its entirety. 
Subsection 230.50(B)(1)(4) - Delete the subsection in its entirety. 

SECTION 230.52 

Section 230.52 - Delete the section in its entirety. 

SECTION 230.54 

Section 230.54 - Delete in its entirety and add a new section 230.54 to read as follows: 
230.54 Overhead Service Locations. 

(A) Raintight Service Head. Service raceways shall be equipped with a raintight service head at the 
point of connection to service-drop conductors. 

(B) Service Heads Above Service-Dron Attachment Service heads shall be located above the point 
of attachment of the service-drop conductors to the building or other structure. 

Exception: Where it is impracticable to locate the service head above the point of attachment the 
service head location shall be permitted not farther than 600 mm (24 in.) from the point of attachment. 

(C) Separately Bushed Opening. Service heads shall have conductors of different potential brought 
out through separately bushed openings. 

(D) Drip Loops. Drip loops shall be formed on individual conductors. To prevent the entrance of water 
service-entrance conductors shall be connected to the service-drop conductors below the level of the 
service head. 

(E) Arranged that Water Will Not Enter Servi™ R aceway or En , nip mP nt Service-drop conductors 
and service-entrance conductors shall be arranged so that water will not enter service racewav or 
equipment. J 



34 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 210.11 through Section 285.25 

SECTION 230.64 

Section 230.64 - Add a new section 230.64 to read as follows: 

230.64 Service Rooms or Areas. 

( A\ General. The minimum sufficient working space shall be as provided in Section 110.26 or 110 34 

as applicable, in order to assure the safety of operation, inspection, and repairs within the vicinity of the 

service equipment. 

Htt Service Equipment Totaling 1Q0 kVA. or Larger. Where service equipment totaling 1000 kVA 

or larger is installed separately, or as part of a switchboard, the room in which such switchboard is 

located shall be constructed of noncombustible materials having a 2 hour fire rating and shall be of 

dimensions adequate to house the switchboard and to provide the following minimum clearances: 

(1) At least 1.5 m (5 ft) in front of the switchboard if it is in one line, and at least 2.1 m (7 ft) in front of 
the board if boards are installed facing each other. 

(2) At least 300 mm (12 in.) from the floor to any energized part of the switchboard, except by special 
permission. 

(3) Where side and/or rear access is required, the following shall also apply: 
• At least 900 mm (3 ft) at each end of the board. 

. At least 900 mm (3 ft) at the rear of the board clear of all obstructions or as specified in Table 
1 10.26(A)(1) or Table 1 10.34(A) as applicable, whichever is greater. 

(4) Front-only accessible switchboards may be installed 300 mm (12 in.) or less from a wall. However, 
if the front-only accessible switchboard is installed more than 300 mm (12 in.) from the wall, access 
must be sealed at each end or comply with the restrictions herein. 

(5) Service equipment shall be arranged so that it is reachable from the entrance door without having to 
pass in front of, or behind any other electrical equipment in the room. This requirement shall be waived 
if a second entrance door is provided and located as remotely as practical from the first. Each door shall 
access an area, which leads to a legal exit. 

SECTTON 230.70 

Subsection 230.70(A)(1) - Revise to read as follows: 

(1) Readily Accessible Location. The service disconnecting means shall be installed at a readily 

accessible location inside of a building or structure nearest the point of entrance of the service 

conductors. 

Exception: Service disconnecting means may be installed on the outside of residential buildings of one 

through four dwelling units. 

Subsection 230.70(B) - Revise to read as follows: 

(K\ Marking. Each service disconnecting means shall be permanently marked to identify it as a service 

disconnect. Each disconnecting means shall be marked to indicate the load served. 



New York City 2011 Electrical Code 



35 



Section 210.11 through Section 285.25 NYC 2011 Electrical Code Technical Provis ions 

SECTION 230.76 

Section 230.76 - Add a new paragraph at the end of section 230.76 to read as follows: 

Where remote control devices are used on service equipment or manually operated circuit breaker devices 
totaling 1000 kVA or larger, it shall be the responsibility of the owner of the building or such owner's 
authorized agent to have the opening and closing mechanism of each service switch or service breaker tested at 
least once every year. The testing need not be performed under load. A record showing the date and signature 
of the qualified person making the test shall be kept posted at the switch or circuit breaker. 

SECTION 230.94 

Section 230.94 - Revise Exception No. 3 to read as follows: 

Exception No. 3: Circuits for load management devices and emergency supply shall be permitted to be 
connected on the supply side of the service overcurrent device where separately provided with 
overcurrent protection. 



ARTICLE 240 
Overcurrent Protection 

SECTION 240.12 

Subsection 240.12(A) - Add a new subsection 240.12(A) to read as follows: 
(A) Service Overcurrent Protective Device. 

Where the service overcurrent protective device (OCPD) rating or setting is above 601 Amps, such 
device shall be selectively coordinated with the next downstream OCPD. 

FPNNo. 1: See definition of "Coordination (Selective)." 

Exception No. 1: Selective coordination shall not be required between two OCPDs in series with one 
another when no loads are connected in parallel with the downstream device. 

Exception No. 2: When the second level OCPD is a single main device having the same rating or setting 
as the service OCPD, selective coordination shall be required between the third level devices and the 
two upstream devices. 

Exception No. 3: Selective coordination shall not be required between transformer primary and 
secondary OCPDs, where only one OCPD exists on the transformer secondary. 

Renumber first paragraph of 240.12 as new subsection 240.12(B), and retitle as follows: 
(B) Orderly Shutdown. 

SECTION 240.86 

Section 240.86 - Add a FPN after first paragraph to read as follows: 
FPN: See 240.12, 700. 27 and 708.54. 



36 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 210 J 1 through Section 285.25 

ARTICLE 250 
Grounding and Bonding 

SECTION 250,52 

Subsection 250.52(A)(1) - Delete the Exception in its entirety. 

ARTICLE 285 

Surge-Protective Devices (SPDs), 1 kV or Less 

SECTION 285.25 

Section 285.25 - Add a FPN at end of paragraph to read as follows: 

FPN: Device to be used as per manufacturer's listing, available fault current should be 
considered. 



New York City 2011 Electrical Code 37 



Section 3 00 J through Section 396 NYC 2011 Electrical Code Technical Provisions 



38 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 300.3 through Section 396 

CHAPTER 3 
Wiring Methods and Materials 

ARTICLE 300 
Wiring Methods 

SECTION 300.3 

Subsection 300.3(C)(1)(a) - Add a new subsection 300.3(C)(1)(a) to read as follows: 

(a) Barriers shall be provided to isolate conductors energized from different sources when system 
voltage exceeds 250 volts nominal and conductors are protected by first or second level overcurrent 
protective devices. Sources include service entrance points, secondaries of different transformers, 
generators and UPS systems. 

SECTION 300.5 

Subsection 300.5(A) - Revise to read as follows: 

(A) Minimum Cover Requirements. Direct-buried cable or conduit or other raceways shall be installed 
to meet the minimum cover requirements of Table 300.5. Direct-buried cable shall not be installed 
except by special permission from the commissioner. 

SECTION 300.6 

Subsection 300.6(B) - Revise to read as follows: 

(B) Aluminum Metal Equipment. Aluminum raceways, cable trays, cablebus, auxiliary gutters, cable 
armor, boxes, cable sheathing, cabinets, elbows, couplings, nipples, fittings, supports and support 
hardware shall not be permitted to be embedded in concrete or come in direct contact with the earth. 

SECTION 300.22 

Subsection 300.22(C) - Revise the first paragraph to read as follows: 

(Q Other Space Used for Environmental Air. This section applies to non-fire rated spaces used for 
environmental air-handling purposes other than ducts and plenums as specified in 300.22(A) and (B). It 
does not include habitable rooms or areas of buildings, the prime purpose of which is not air handling. 



New York City 2011 Electrical Code 3 9 



Section 300.3 through Section 396 NYC 2011 Electrical Code Technical Provisions 

ARTICLE 328 

Medium Voltage Cable: Type MV 

SECTION 328.10 

Section 328.10 - Revise to read as follows: 

328.10 Uses Permitted. Type MV cables shall be permitted for use on power systems rated up to 
35,000 volts nominal as follows: 

(1) In wet or dry locations, 

(2) In raceways. 

SECTION 328.12 

Section 328.12 - Revise to read as follows: 

328.12 Uses Not Permitted. Type MV cable shall not be used: 

(1) Where exposed to direct sunlight, 

(2) In cable trays, 

(3) Direct-buried, 

(4) In messenger-supported wiring. 

SECTION 328.80 

Section 328.80 - Delete the last sentence. 

ARTICLE 330 

Metal-Clad Cable: Type MC 

SECTION 330.10 

Subsection 330.10(A)(1) - Delete the word "services." 

Subsection 330.10(A)(3) - Delete the words "or outdoors." 

Subsection 330.10(A)(5) - Revise to read as follows: 

To be direct-buried where identified for such use and by special permission. 

Subsection 330.10(A)(8) - Delete the subsection in its entirety. 

Subsection 330.10(B)(3) - Delete the subsection in its entirety. 



40 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 300.3 through Section 396 

SECTION 330.12 

Section 330.12 -Revise the first sentence to read as follows: 

330.12 Uses Not Permitted. Type MC cable shall not be used under any of the following conditions: 

Subsection 330.12(3) - Add a new subsection 330.12(3) to read as follows: 

(3) Where used as service conductors. 

Subsection 330.12(4) - Add a new subsection 330.12(4) to read as follows: 

(4) Where the cable has an outer jacket of PVC, in residential buildings exceeding three floors above grade. 
Subsection 330.12(5) - Add a new subsection 330.12(5) to read as follows: 

(5) Where the cable has an outer jacket of PVC, in any nonresidential building unless concealed within 
non-plenum walls, floors and ceilings where the walls, floors and ceilings provide a thermal barrier of 
material that has at least a one hour rated assembly as identified in listings of fire rated assemblies. 

ARTICLE 334 

Nonmetallic-Sheathed Cable: Types NM. NM C. and NMS 

SECTION 334.10 

Section 334.10 - Revise to read as follows: 

334.10 Uses Permitted. Type NM, Type NMC, and Type NMS cables shall be permitted to be used in 

the following: 

(1) One- and two-family dwellings. 

(2) Multifamily dwellings, except as prohibited in Section 334.12. 

FPN: See Section 310.10 for temperature limitation of conductors. 
Subsection 334.10(A)(1) - Revise to read as follows: 
(1) For both exposed and concealed work in normally dry locations. 
Subsection 334.10(B)(1) - Revise to read as follows: 

(1) For both exposed and concealed work in dry, moist, damp or corrosive locations. 
Subsection 334.10(C)(1) - Revise to read as follows: 
(1) For both exposed and concealed work in normally dry locations. 

SECTION 334.12 

Subsection 334.12(A)(1) - Revise to read as follows: 

(I) In any multifamily dwelling exceeding three floors above grade. 
Subsection 334.12(A)(1) -Delete the Exception in its entirety. 

Subsection 334.12(A)(1 1) - Add a new subsection 334.12 (A)(l 1) to read as follows: 

(I I) In non-residential buildings. 



New York City 2011 Electrical Code 



41 



Section 300.3 through Section 396 NYC 2011 Electrical Code Technical Provisions 

SECTION 334.15 

Subsection 334.15(B) - Change reference from 300.4(E) to 300.4(F). 

SECTION 334.30 

Subsection 334.30(C) - Delete the subsection in its entirety. 

ARTICLE 336 

Power and Control Trav Cable; Type TC 

SECTION 336.10 

Subsection 336.10(6) - Delete the subsection in its entirety. 

SECTION 336.12 

Subsection 336.12(5) - Add a new subsection 336.12 (5) to read as follows: 
(5) As fire alarm circuit wiring. 

SECTION 336.104 

Subsection 336.104(A) - Delete the subsection in its entirety. 

ARTICLE 338 

Service-Entrance Cable: Types SE and USE 

SECTION 338.10 

Subsection 338.10(A) - Add a second sentence to read as follows: 

Where installed as service entrance conductors, Type SE cable shall be enclosed in a threaded metallic 
conduit. 

Subsection 338.10(B)(2) - Delete the Exception in its entirety. 
Subsection 338.10(B)(4)(b) - Revise to read as follows: 

(b) Exterior Installations. In addition to the provisions of this article, service-entrance cable 
used for feeders or branch circuits, where installed as exterior wiring, shall be installed in a 
threaded metallic conduit. 



42 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 300.3 through Section 396 

ARTICLE 340 

Underground Feeder and Branch-Circuit Cable: Type UF 

SECTION 340.10 

Subsection 340.10(1) - Revise to read as follows: 
(1) For use underground. For underground requirements, see 300.5. 
Subsection 340.10(5) - Delete the subsection in its entirety. 
Subsection 340.10(6) - Delete the subsection in its entirety. 

SECTION 340.12 

Subsection 340.12(12) - Add a new subsection 340.12(12) to read as follows: 

(12) Direct burial. 

Subsection 340.12(13) - Add a new subsection 340.12(13) to read as follows: 

(13) For Solar Photovoltaic Systems. 

SECTION 344.10 

Subsection 344.10(A)(3) - Revise the second sentence of subsection 344.10(A)(3) to read as follows: 
Aluminum RMC shall not be permitted to be encased in concrete or used for direct burial. 
Subsection 344.10(B)(2) - Delete the subsection in its entirety. 

ARTICLE 350 

Liauidtight Flexible Metal Conduit: Type LFMC 

SECTION 350.12 

Subsection 350.12(3) - Add a new subsection 350.12(3) to read as follows: 
(3) In lengths exceeding 1.83m (6 ft). 



New York City 2011 Electrical Code 43 



Section 300 J through Section 396 NYC 2011 Electrical Code Technical Provisions 

ARTICLE 352 

Rigid Polyvinyl Chloride Conduit: Type PVC 

SECTION 352.10 

Subsection 352.10(1) - Add a new subsection 352.10(1) to read as follows: 

(I) Residential Use. In any residential building or dwelling unit not exceeding three floors above 
grade. 

Subsection 352.10(J) - Add a new subsection 352.10(J) to read as follows: 

(J) Non Residential Use . Unless prohibited elsewhere by other articles of this code, PVC conduit shall 
be permitted in any nonresidential building or residential building over 3 stories high. Rigid nonmetallic 
conduit shall be concealed within non-plenum walls, floors and ceilings where the walls, floors and 
ceilings provide a thermal barrier of material that has at least a one hour rated assembly as identified in 
listings of fire-rated assemblies. 

ARTICLE 354 

Nonmetallic Underground Conduit with Conductors: Type NUCC 

SECTION 354.10 

Section 354.10 - Revise the heading and the first sentence to read as follows: 

354.10 Uses Permitted by Special Permission Only. The use of NUCC and fittings shall be permitted 
by special permission only, as follows: 

ARTICLE 355 

Reinforced Thermosetting Resin Conduit: Type RTRC 

SECTION 355.10 

Subsection 355.10(1) -Add a new subsection 355.10(1) to read as follows: 

(I) Residential Use. In any residential building or dwelling unit not exceeding three floors above grade. 

Subsection 355.10(J) - Add a new subsection 355.10(J) to read as follows: 

(J) Non R esidential Use. Unless prohibited elsewhere by other articles of this code, RTRC conduit 
shall be permitted in any nonresidential building or residential building over 3 stories high. RTRC 
conduit shall be concealed within non-plenum walls, floors and ceilings where the walls, floors and 
ceilings provide a thermal barrier of material that has at least a one hour rated assembly as identified in 
listings of fire-rated assemblies. 



44 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 300.3 through Section 396 

ARTICLE 356 

Liquidtight Flexible Nonmetallic Conduit: Type LFNC 

SECTION 356.10 

Section 356.10 - Revise the heading and the first sentence to read as follows: 

356.10 Uses Permitted by Special Permission Only. The use of LFNC shall be permitted by special 
permission only, as follows: 

ARTICLE 358 

Electrical Metallic Tubing: Type EMT 

SECTION 358.10 

Subsection 358.10(C) - Delete the subsection in its entirety. 

SECTION 358.12 

Subsection 358.12(7) - Add a new subsection 358.12(7) to read as follows: 
(7) For underground or exterior installations or in wet locations. 

ARTICLE 362 

Electrical Nonmetallic Tubing: Type ENT 

SECTION 362.10 

Section 362.10 - Revise to read as follows: 

362.10 Uses Permitted. The use of electrical nonmetallic tubing and fittings shall be permitted: 

(1) Concealed within walls, floors, and ceilings where the walls, floors, and ceilings provide a thermal 
barrier of material which has at least a 1 hour finish rating as identified in listings of fire-rated 
assemblies. 

(2) In locations subject to severe corrosive influences as covered in 300.6 and where subject to 
chemicals for which the materials are specifically approved. 

(3) In concealed, dry, and damp locations not prohibited by 362.12. 

(4) Above suspended ceilings where the suspended ceilings provide a thermal barrier of material, which 
has at least a 1 hour finish rating as identified in listings of fire-rated assemblies. 

(5) Embedded in poured concrete, provided fittings approved for this purpose are used for connections. 

(6) For wet locations indoors or in a concrete slab on or below grade, with fittings listed and approved 
for the purpose. 



New York City 201 1 Electrical Code 45 



Section 300. 3 through Section 396 NYC 2011 Electrical Code Technical Provisions 

FPN No. 1: Extreme cold may cause some types of nonmetallic conduits to become brittle and, 
therefore, more susceptible to damage from physical contact. 

FPN No. 2: Extreme cold may cause some types of nonmetallic tubing to become brittle and, 
therefore, more susceptible to damage from physical contact. 

SECTION 362.12 

Subsection 362.12(1 1) - Add a new subsection 362.12(1 1) to read as follows: 
(1 1) In ducts, plenums and other air handling spaces. 

ARTICLE 366 
Auxiliary Gutters 

SECTION 366.10 

Subsection 366.10(B) - Revise the first sentence to read as follows: 

Nonmetallic auxiliary gutters may only be installed by special permission and shall be listed for the 
maximum ambient temperature of the installation and marked for the installed conductor insulation 
temperature rating. 

ARTICLE 368 
Busways 

SECTION 368.2 

Section 368.2 - Change title from "Definition" to " Definitions" and add a new definition to read as 
follows: 

Service Busway. For the purpose of this article, service busway is busway used to connect from the 
service point to the line terminals of the service equipment. 

SECTION 368.119 

Section 368.1 19 - Add a new section 368.1 19, after the heading "III. Construction," to read as follows: 

368.119 Service Busway. Service busway shall conform to the specifications listed in (A) through (I) 
below. 

(A) Ampacity and Ratings of Busbars. Ampacity and ratings of busbars shall be in accordance with 
230.42(A). 

(B) Length. Service busway shall be limited to a maximum of 3.0 m (10 ft) in length. 
Exception: By special permission. 



46 New York City 2011 Electrical Code 



NYC 2011 Electrical Co de Technical Provisions Section 300.3 through Section 396 

fO Insulation. Busbars shall be insulated with a material listed for the purpose and rated for use at a 

minimum of 600 Volts. 

Exception: Bolted busbar joints requiring maintenance shall be permitted to be uninsulated. 

(m Enclosure. Enclosure shall be fabricated from aluminum, minimum 3.2 mm (1/8 in.) thick or other 

non-magnetic material approved by the commissioner. 

(V?> Enclosure Vents. Ventilating openings shall be permitted in the sides and bottom of the enclosure. 

Top of enclosure must be solid. 

(¥) Mounting. Busbars shall be mounted on insulating supports, properly spaced and braced to 

withstand the maximum available short circuit current. 

(G\ Clearance. A minimum clearance of 102 mm (4 in.) shall be provided from the phase bars to the 

enclosure. 

fm Plating. All busbar joints and connections shall be plated with silver, tin or nickel. 

m Accessibility. All busbar joints and connections shall be accessible. 

ARTICLE 370 
Cablebus 



SECTION 370.3 

Section 370.3 - Delete "and services" from the last sentence of the first paragraph, so that it reads as 

follows: 

Cablebus shall be permitted to be used for branch circuits and feeders. 

ARTICLE 376 
Metal Wirewavs 

SECTION 376.22 

Section 376.22 - Add an Exception after subsection (B) to read as follows: 

Exception: Metallic auxiliary gutters may contain up to 40 service entrance conductors without 

applying derating factors. 



New York City 2011 Electrical Code 



47 



Section 300.3 through Section 396 NYC 2011 Electrical Code Technical Provisions 

ARTICLE 378 
Nonmetallic Wirewavs 

SECTION 378. in 

Section 378.10 - Revise the heading and first sentence of the section to read as follows: 

378.10 Uses Permitted by Special Permission Only. The use of nonmetallic wireways shall be 
permitted by special permission only as follows: 

ARTICLE 380 
Multioutlet Assembly 

SECTION 380.2 

Subsection 380.2(B)(7) - Add a new subsection 380.2(B)(7) to read as follows: 
(7) Where cord and plug connected unless listed for the purpose. 

ARTICLE 382 
Nonmetallic Extensions 

SECTION 382 TT 

Section 382 II [ - After subheading "II. Installation" of the Article, add a sentence to read as follows and 
delete remainder of the Article: 

II. Installation 

Installation of non-metallic extensions shall not be permitted. 

ARTICLE 388 

Surface Nonmetallic Raceway s 

SECTION 388.12 

Subsection 388.12(8) - Add a new subsection 388.12(8) to read as follows: 

(8) In residential buildings exceeding three floors above grade. 
Subsection 388.12(9) - Add a new subsection 388.12(9) to read as follows: 

(9) In non-residential buildings. 



48 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions ^ Section 3003 through Section 396 

ARTICLE 392 

Cable Trays 

Subsection 392.3(E) - Add a new sentence at end of existing paragraph to read as follows: 
Nonmetallic cable trays may be used by special permission only. 

ARTICLE 394 

Concealed Knob-and-Tube Wiring 

SECTION 394 II 

Section 394 II - After subheading "II. Installation" of this Article, add a sentence to read as follows and 
delete the rest of the Article: 

II. Installation 

Installation of Concealed Knob-and-Tube Wiring shall not be permitted. 

ARTICLE 396 
Messenger-Supported Wiring 

SECTION 396 

Table 396.10(A) - Delete second line of Table in its entirety. 



New York City 201 1 Electrical Code 49 



Section 404.10 through Section 450.46 NYC 2011 Electrical Code Technical Provisions 



50 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technic al Provisions Section 404.10 through Section 450.46 

CHAPTER 4 
Equipment for General Use 

ARTICLE 404 
Switches 

SECTION 404.10 

Subsection 404.10(A) - Delete the subsection in its entirety. 

ARTICLE 408 

Switchboards and Panelboards 



SECTION 408.60 

Section 408.60 - Add new section 408.60 to read as follows: 

408.60 Special Requirements. Switchboards shall be listed, approved and constructed in accordance 

with UL 891, Eleventh Edition, Standard for Switchboards. Panelboards shall be listed, approved and 

constructed in accordance with UL 67, Eleventh Edition, Standard for Panelboards. Additional 

construction specifications shall be in accordance with (A) thru (G) below. 

( A1 Neutral Disconnect Link in Service Switchboards. A bus link shall be provided for disconnecting 

the neutral service conductor(s) from the outgoing load neutral conductor(s). Such disconnect link shall 

be readily accessible and located downstream of the main bonding jumper and grounding electrode 

conductor terminal. In a multi-section switchboard a single neutral disconnect link may be provided for 

all service disconnects. 

Exception: A single cable lug accommodating a maximum of two cables may be used in lieu of a neutral 

disconnect link for service disconnects 800 amperes or less. 

(m Dielectric Test. All service and distribution equipment, switchboards, control panels, and panelboards 

shall be given a 60 Hz AC dielectric test, phase to phase and phase to ground, at twice rated voltage plus 

1,000 volts for one minute (minimum 1500 volts) prior to shipment from factory. A dielectric test voltage 

which is 20 percent higher than that in the one minute test may be applied for one second as an alternative to 

the one minute test. The date of the test and the name and title of the individual certifying the test shall be 

clearly shown on a label affixed to the equipment. 

(O Warning Label. All 480/277 volt switchboards, panelboards and panelboard back boxes shall have 

a visible label, clearly marked "WARNING 480/277 VOLTS" and in compliance with ANSI Standard 

Z535.4. 



New York City 2011 Electrical Code 



51 



Section 404.10 through Section 450.46 NYC 2011 Electrical Code Technical Provisions 

(D) Grounding Switchboard Frames. Switchboard frames and structures supporting switching equipment 
shall be grounded. A multisection switchboard shall be provided with an internal ground bus, which will 
electrically connect all of the sections of the switchboard. This ground bus shall have a minimum cross 
section of V 2 square inch of copper or 3 / 4 square inch of aluminum. The contact surfaces of the equipment 
ground connections shall provide an effective electrical ground path for fault currents. 

Exception: Frames of direct current, single-polarity switchboards shall not be required to be grounded 
if effectively insulated. 

(E) Busbars. 

(1) General. Busbars shall be sized based on 1000 amperes per square inch for copper and 750 amperes 
per square inch for aluminum. 

Exception: In service switchboards, generator paralleling switchboards and when connecting to devices 
rated over 2500 amperes. See 408.60(E)(2) and (E)(3) below. 

(2) In Service Equipment And Switchboards Supplied Directly From Separately Derived Systems. 

Line-side busbars in service switchboards and all busbars in generator paralleling switchboards shall be 
considered service conductors and shall comply with the requirements of 230.42(A). 

(3) Connection to Devices Rated over 2500 Amperes. Busbars shall be sized in accordance with (a) 
and (b) below when connected to a device (switch or circuit breaker) over 2500 amperes: 

(a) Over 2500 amperes but less than 5000 amperes, busbars shall be sized based on 800 amperes 
per square inch for copper and 600 amperes per square inch for aluminum. 

(b) 5000 amperes and over, busbars shall be sized based on 700 amperes per square inch for 
copper and 525 amperes per square inch for aluminum. 

Exception: Beyond a minimum distance of 1.2m (4 ft) along the current path from the device, the busbar 
may be reduced in size, in accordance with 408.60(E)(1) above. 

(4) Ampacity of Through (Main) Bus. The through (main) bus that feeds four or more overcurrent 
protective devices of a switchboard shall have a minimum ampacity of 70 percent of the sum of the 
frame ratings of all devices fed by that through bus. If provisions are made for the addition of 
overcurrent protective devices in the future, the expected overcurrent protective device ratings shall be 
included in the above calculations. The through bus ampacity shall not be required to be greater than the 
frame rating of the upstream overcurrent protective device. 

Exception: In service equipment and switchboards supplied directly from separately derived systems 
and for devices rated over 2500 amperes refer to 408.60(E)(2) and (E)(3) above. 

(5) Ampacity of Section Bus. The section bus is that portion of the bus that serves one or more 
overcurrent protective devices in the switchboard section and includes that part of the bus between the 
through bus and the branch distribution bus. The minimum ampacity of the section bus of a switchboard 
shall be determined by the table below. The section bus ampacity shall not be required to be greater than 
that of the through bus. 



52 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions 



Section 404.10 through Section 450.46 



Total Number of Branch Overcurrent Devices 



1-2 



3-4 



Over 4 



Minimum Ampacity of Section Bus as a 

percentage of the Sum Total of Branch 

Overcurrent Devices* 



100 



80 



70 



*For fusible switches, the maximum fuse size shall be used. For interchangeable trip circuit breakers, the 
maximum trip rating shall be used. If provisions are made for the future installation of branch 
overcurrent protective devices, the ampacity of these units shall be included in the calculation. 
Exception: In service equipment and switchboards supplied directly from separately derived systems 
and for devices rated over 2500 amperes refer to 408.60(E)(2) and (E)(3) above. 
(6) Busbar Joints. All busbar joints and connections shall be plated with silver, tin or nickel The 
current density at contact surfaces in busbar joints shall not exceed 200 amperes per square inch for 
copper and 150 amperes per square inch for aluminum. A permanent label providing torque values or 
tightening instructions for all busbar joints shall be affixed to each section of a switchboard. 
<Y\ Hinged Doors. Freestanding switchboards, which have rear access, shall have hinged rear doors 
fastened by captive screws or suitable latches. 

(G\ Barriers In Switehhnards Rate d Over ISO Volts To Ground. Listed and approved barriers shall 
be placed between adjacent sections of the switchboard. Listed and approved barriers shall be placed 
between the switchboard and its pullbox, whether located at the top or bottom of the equipment. All 
openings in the barriers for busbars and cables shall be closed with snug fitting, listed and approved non- 
hygroscopic, arc resistant material. 



ARTICLE 409 
Industrial Control Panels 

SECTION 409.108 

Section 409.108 - At the end of the first paragraph, add "and shall comply with section 408.60." 

ARTICLE 410 

Liiminaires. Landholders , and Lamps 

SECTION 410.30 

Subsection 410.30(B)(1) - At the first sentence, insert "intended for use in a wet location" between "A 
pole" and "shall have" 



New York City 2011 Electrical Code 



53 



Section 404.10 through Section 450.46 NYC 2011 Electrica l Code Technical Provisions 

SECTION 410.151 

Subsection 410.151(B) - Number the existing FPN as FPN No.l, and add a second FPN to read as 
follows: 

FPN No. 2 : See the applicable Energy Conservation Code. 

ARTICLE 422 
Appliances 

SECTION 422.12 

Section 422.12 - Revise to read as follows: 

422.12 Central Heating Equipment. Central heating equipment other than fixed electric space-heating 
equipment shall be supplied by an individual branch circuit. 

Exception No. 1: Auxiliary equipment, such as a pump, valve, humidifier, or electrostatic air cleaner 
directly associated with the heating equipment, may be connected to the same branch circuit. 

Exception No. 2: Permanently connected air-conditioning equipment may be connected to the same 
branch circuit. 

(A) Low Pressure Boiler. Any steam boiler operating at 15 psig or less, any hot water boiler operating 
below 1 60 psig, or any boiler rated at 1 horsepower or less, regardless of pressure. 

(B) Controls on Low Pressure Boilers. An electrical pressure switch with normally closed contacts 
shall be connected to the steam drum of every boiler ahead of all valves. The pressure switch shall be set 
to open at safe working pressure of the boiler. This boiler electrical high-pressure cut-off switch shall be 
designed to reclose only by a reset device, which shall be manually controlled. One and two family 
residences are exempt from these provisions. 

(C) Circuit Voltage and Safety Devi ces Connections. Conductors of the control circuits shall only be 
connected to circuits not exceeding 150 volts to ground, or not more than 150 volts between conductors. 

All safety devices, such as pressure controls, fire controls, relays, etc. shall have their electric switching 
mechanism connected to the ungrounded conductor. 

SECTION 422.16 

Subsection 422.16(B)(4) - Replace the term "range hood(s)" with the term "combination range 
hood/microwave oven(s)" in the title, first paragraph and the Exception. 



54 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 404.10 through Section 450.46 

ARTICLE 430 

Motors. Motor Circuits, and Controllers 

SECTION 430.5 

Table 430.5 - Add the following items to the Table: 
"Services 230" and "Switchboards and Panelboards 408" 

SECTION 430.95 

Section 430.95 - At the end of the first paragraph add a new sentence to read as follows: 

When the equipment is utilized as service equipment, a means for disconnecting the neutral service 

conductor(s) complying with 408.60(A) is required. 

SECTION 430.97 

Section 430.97 - After the title, add a new sentence to read as follows: 

When the equipment is utilized as service equipment, the busbars shall comply with 408.51. 

ARTICLE 450 

Transformers and Transformer Vaults (Including Sec ondary Ties^ 

SECTION 450.9 

Section 450.9 - Add a new third paragraph to read as follows: 

Mechanical ventilation and/or air conditioning shall be provided and shall be adequate to dispose of the 

transformer full-load losses without exceeding 40°C (104°F) ambient temperature in the room. 

SECTION 450.25 

Section 450.25 - Delete the section in its entirety. 

SECTION 450.42 

Section 450.42 - Revise to read as follows: 

450.42 Walls, Roofs and Floors. The vault shall be of such dimension as to permit the installation of 
all electrical equipment in accordance with 110.26 or 110.34 as applicable. The vault shall be of 
fireproof construction with a minimum fire resistance rating of three hours with floors, walls and 
ceilings 152 mm (6 in.) thick if made of concrete, or 203 mm (8 in.) thick if made of brick, or 203 mm 
(8 in.) thick if made of filled cement block. All building steel forming part of the vault construction shall 
have a comparable fire resistance rating. Each compartment within a vault shall be built to the same 



New York City 2011 Electrical Code 55 



Section 404.10 through Section 450.46 NYC 2011 Electrical Code Technical Provisions 

specifications in respect to the thickness of walls and fireproof door, as the vault. The floors shall be of 
ample strength to carry the weight of the equipment to be installed in the vault. The floors and wall, to 
the height of the sill, shall be given a hard impervious finish and painted to prevent the absorption of oil. 

Exception; Where transformers are protected with automatic sprinkler, carbon dioxide, or gas 
suppression system, construction of 1 -hour rating shall be permitted. 

SECTION 450.43 

Subsection 450.43(A) - Delete the FPN, and revise the subsection and Exception to read as follows: 

(A) Type of Door. Each doorway leading into a vault from the building interior shall be provided with 
a tight-fitting door that has a minimum fire rating of 3 hours. Where practicable, basement vaults or 
vaults opening up on a roof shall be provided with an outside entrance so that no entrance directly into 
the vault from the interior of the building will be necessary. Where entrance into the vault is from the 
interior of the building, the vault shall open upon a vestibule, passage hall or switchboard room not 
commonly in public use. 

Exception: Where transformers are protected with automatic sprinkler, carbon dioxide, or gas 
suppression system, construction of 1 -hour rating shall be permitted. 

SECTION 450.45 

Section 450.45 - Revise the first paragraph to read as follows: 

A system of ventilation shall be provided to dispose of transformer full load losses and maintain a vault 
ambient temperature not to exceed 40°C (104°F). Minimum criteria for ventilation shall be in 
accordance with (A) through (F) below: 

Subsection 450.45(C) - Add an Exception to read as follows: 

Exception: Where required to meet the ventilation conditions of this section, the minimum of three 
square inches per kVA of natural ventilation may be supplemented by a dedicated mechanical 
ventilation system. 



SECTION 450.46 

Section 450.46 - Revise to read as follows: 

450.46 Drainage. Where practicable, vaults containing more than 100 kVA transformer capacity shall 
be provided with a drain or other means that will carry off any accumulation of oil or water in the vault 
unless local conditions make this impracticable. The floor shall be pitched to the drain where provided. 
Drainage shall be permitted to carry off water accumulation. Such drainage shall prevent drainage of 
transformer coolant into the water drainage system and shall be provided in accordance with the New 
York City Construction Codes and other authorities having applicable regulations. 



56 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 500. 8 through Section 590. 8 

CHAPTER 5 
Special Occupancies 

ARTICLE 500 

Hazardous (Classified) Locations, Classes I, II, and III, Divisions 1 and 2 

SECTION 500.8 

Subsection 500.8(A)(3) - Revise to read as follows: 

(3) Evidence acceptable to the authority having jurisdiction. 

ARTICLE 501 
Class I Locations 

SECTION 501.10 

Subsection 501.10(B)(1)(7) - Delete the words "and Schedule 80 PVC conduit, factory elbows, and 
associated fittings" from the first paragraph. 

Subsection 501.10(B)(2) - Delete item (4) "Liquidtight flexible nonmetallic conduit with listed fittings." 

ARTICLE 502 
Class II Locations 

SECTION 502.10 

Subsection 502.10(A)(2) - Delete item (3) "Liquidtight flexible nonmetallic conduit with listed fittings." 

SECTION 502.100 

Subsection 502.100(B)(2) - Revise to read as follows: 

(2) Containing Askarel. The use of transformers containing Askarel is prohibited. Delete (1), (2), (3). 



New York City 2011 Electrical Code 57 



Section 500.8 through Section 590.8 NYC 2011 Electrical Code Technical Provisions 

ARTICLE 503 
Class III Locations 

SECTION 503.10 

Subsection 503.10(A) - Delete the words "rigid nonmetallic conduit." 

Subsection 503.10(A)(2) - Delete the words "liquidtight flexible nonmetallic conduit with listed fittings." 

ARTICLE 505 

Class I, Zone 0, 1, and 2 Locations 

SECTION 505.15 

Subsection 505.15(C)(1)(g) - Delete the words "and Schedule 80 PVC conduit, factory elbows, and 
associated fittings." 

Subsection 505.15(C)(2) - Delete the words "liquidtight flexible nonmetallic conduit with listed fittings." 

ARTICLE 506 

Zone 20, 21, and 22 Locations for Combustible Dusts or 

Ignitable Fibers/Flyings 

SECTION 506.9 

Subsection 506.9(A)(3) - Delete the words "such as a manufacturer's self-evaluation or an owner's 
engineering judgment." 

SECTION 506.15 

Subsection 506.15(A)(5) - Delete the words "liquidtight flexible nonmetallic conduit with listed fittings." 

ARTICLE 511 

Commercial Garages, Repair and Storage 

SECTION 511.7 

Subsection 511.7(A)(1) - Delete the words "rigid nonmetallic conduit, electrical nonmetallic tubing" 
and "or liquidtight flexible nonmetallic conduit." 



58 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 500.8 through Section 590.8 

ARTICLE 515 
Bulk Storage Plants 

SECTION 515.7 

Subsection 515.7(A) - Delete the words, "Schedule 80 PVC conduit." 

ARTICLE 516 

Spray Application, Dipping and Coating Processes 

SECTION 516.3 

Subsection 516.3(C)(2)(a) - Revise to read as follows: 

(a) The exhaust ventilation system shall be interlocked with the spray application equipment, the 
Division 2 or Zone 2 location shall extend 1.5 m (5 ft) horizontally and 900 mm (3 ft) vertically 
from the open face or open front of the booth or room, as shown in figure 516.3(B)(2), top. 

Subsection 516.3(C)(2)(b) - Delete the subsection in its entirety. 

ARTICLE 517 
Health Care Facilities 

SECTION 517.30 

Subsection 5 1 7.30(B)(4) - At the end of the paragraph, add the following: 
A separate automatic transfer switch shall be required for: 

(1) The fire pump. For fire pump requirements refer to Article 695 - Fire Pumps. 

(2) Alarm and alerting systems. 

(3) Automatic smoke control or venting. 

(4) Stair pressurization systems. 

FPN Figures 517.30, No.l and 517.30, No.2, add the following: 
This figure does not reflect the switches and automatic transfer switches required above. 
Subsection 517.30(C)(3)(1) - Delete the words, "or Schedule 80 PVC conduit." 



New York City 201 1 Electrical Code 59 



Section 500.8 through Section 590.8 NYC 2011 Electrical Code Technical Provisions 

SECTION 517.41 

Subsection 517.41(B) - At the end of the paragraph, add the following: 
A separate automatic transfer switch shall be required for: 

(1) The fire pump. For fire pump requirements refer to Article 695 - Fire Pumps. 

(2) Alarm and alerting systems. 

(3) Automatic smoke control or venting. 

(4) Stair pressurization systems. 

FPN Figures 517.41, No.l and 517.41, No. 2, add the following: 

This figure does not reflect the switches and automatic transfer switches required above. 



ARTICLE 518 
Assembly Occupancies 

SECTION 518.1 

Section 518.1 - Revise to read as follows: 

518.1 Scope. This article covers all buildings or portions of buildings or structures, classified as 
Assembly Occupancies in the New York City Construction Codes. 

SECTION 518.2 

Subsection 518.2(A) - Delete the first sentence and replace with the following: 

(A) General. Assembly Occupancies shall be classified as places of assembly in accordance with New 
York City Construction Codes and the Fire Code (under Titles 28 & 29 of the New York City 
Administrative Code) and shall include the following: 

Subsection 518.2(B) - Revise to read as follows: 

(B) Multiple Occupancies. Multiple occupancies shall be classified in accordance with the New York 
City Construction Codes. 

SECTION 518.4 

Subsection 518.4(B) - Delete the subsection in its entirety. 
Subsection 518.4(C) - Delete the subsection in its entirety. 



60 New York City 2011 Electrical Code 



, . , „ • • o Section 500.8 through Section 590.8 
NYC 2011 Electri cal Code Technical Provisions ^ cnon 3(/(A0 * _ 

ARTICLE 520 

T u^^, An^iPnr. Areas of M otion Pictu re and Television Studios, 

performance Are?*, and Similar Locations 



SFCTTON 520.5 

Subsection 520.5(C) - Delete the subsection in its entirety. 

SFCTION 520 6 

Section 520.6 -Delete the words "rigid nonmetallie conduit as pemtitted in this article," from the first 

sentence. 



ARTTCLE 522 

rnntrol Svsten™ for Permanent Amusement Attractions 



SFCTTON 522.1 . 

Subsection 522.1 - Before "electrical equipment" insert the words "(new and existing). 



ARTICLE 525 

r^miv*l S l Circuses. Fairs, and Similar Events 

ST TTTON 525.20 ,,,.,_ a 

Subsection 525.20(G) - In the first sentence, de!ete the words "pe^itted ,0 be" and add the word 

"secured" in front of "nonconductive matting. 



61 



New York City 2011 Electrical Code 



Section 500.8 through Section 590.8 mrr wi m *• ,^ Jr ^ , 

— ° NYC 2011 Electrical Code Techni cal Provisions 

ARTICLE 545 

Manufactured Building s 

SECTION 54*.* 

Section 545.3 - Add new section 545.3 to read as follows- 

SECTION 545.4 

Subsection 545.4(A) - Revise to read as follows: 

(A) Methods Permitted The wiring shall be installed in accordance with the requirements of Chapter 3. 

SECTION 545.fi 

Section 545.6 - Delete the Exception in its entirety. 

SECTION 545. in 

Section 545.10 - Delete the section in its entirety. 

ARTICLE 547 
Agricultural Building 

SECTION 547 5 

Subsection 547.5(A) - Delete the words "liquidtight flexible nonmetallic conduit » 
Subsection 547.5(D) - Delete the words "liquidtight flexible nonmetallic conduit." 

ARTICLE 55ft 

Mobile Homes, Manufactured Hn mWl »n d Mohilo U nm » Po^ 

SECTION 55» 3 

Section 550.3 - Add a new section 550.3 to read as follows- 



62 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 500.8 throug h Section 590.8 

ARTICLE 590 
Temporary Installations 

SECTION 590.4 

Subsection 590.4(J) - Add the following at the beginning of the subsection: 

Temoorary wiring for lighting shall be properly and substantially supported on noncombustible, 

LXoSvrSators and shall be kept off the floor and free and clear of contact with woodwork, 

metal pipes and metal portions of the building structure. 

Subsection 590.4(K) - Add a new subsection 590.4(K) to read as follows: 

n n P^nent Fee^ ™H Branch ™»H» nsed for Temporary T,i P ht and Power. Permanent 

feVders ma^ be used for temporary light, heat or power service if run in approved raceways or conduit 

from the source of supply directly to the distribution center. Temporary polarized lamphoders may be 

connected to permanent branch circuit wiring pending the erection of the permanent fixtures. 

Subsection 590.4(L) - Add a new subsection 590.4(L) to read as follows: 

n/> Grounding. All portable machines shall be grounded. All grounding shall conform with Article 250. 

SECTION 590.6 

Section 590.6 - Add an Exception after the first paragraph, to read as follows: 

Fxcevtion- Temporary wiring installations that are accessible to the public and used to supply 
TlCan poZfrr illumination of outdoor areas during construction, remodehng ™—^r 
repair or demolition of buildings, structures, equipment, or similar activities shall comply with all other 
r! q Zrements of this code for permanent wiring and shall be provided with ground-fault protectron for 

personnel. 

SECTION 590.8 

Section 590.8 - Add a new section 590.8 to read as follows: 

590 8 Sidewalk Shed Lighting. All sidewalk shed lighting installations shall comply with the following 

conditions in addition to all other relevant provisions of this code: 

(1) Such lighting shall be installed in a metal raceway approved for outdoor use. 

(2) All junction boxes shall be suitable for damp or wet locations. 

(3) A minimum wire size of 12 AWG shall be used for the installation. 

(4) All fixtures shall be suitable for outdoor locations. 

(5) Ground-Fault Circuit Interrupter (GFCI) protection is required on receptacles and lighting. 

(6) The installation shall be properly grounded and bonded. 

(7) The panel supplying power to the sidewalk shed lighting shall have a directory that clearly indicates 
which circuit is being used to supply power. 



New York City 2011 Electrical Code 



63 



Section 600.3 through Section 695.14 NYC 2011 Electrical Code Technical Provisions 



64 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 600.3 through Section 695.14 

CHAPTER 6 
Special Equipment 

ARTICLE 600 

Electric Signs and Outline Lighting 

SECTION 600.3 

Section 600.3 - Add the following subsections: 

(C\ Inspection. Electric signs manufactured for installation in the city shall be inspected by the 

department and approved prior to installation. The department may direct that such inspection take place 

at the factory before final assembly or at the place of installation. 

(I» Relocated Signs. The relocation of an approved sign from one location to another may be permitted 

without inspection provided that no alterations in or additions to the existing sign are made, and the 

application to connect at the new location shows the previous location, lettering, and the connected 

electrical load of the sign. 

m Plastic Materials. All plastic materials to be used in the manufacture of electric signs shall be 

submitted for approval. 

(F\ Markings. Each individual plastic section or letter shall be permanently marked with the material 

manufacturer's name, trademark, or other identification symbol. 

(G^ Receptacles. Only receptacles for sign maintenance shall be installed in or on sign enclosures. 

SECTION 600.7 

Subsection 600.7(B)(7)(a) - Replace "14 AWG" with "12 AWG." 

SECTION 600.8 

Subsection 600.8(C) - Revise to read as follows: 

(C\ Minimum Thickness of Enclosure Metal. Sheet steel shall be at least 0.635mm (0.0250 in./24 

U.S.S.G.) thick. Sheet copper or aluminum shall be of equivalent strength. 



New York City 2011 Electrical Code 



65 



Section 600.3 through Section 695.14 NYC 2011 El ectrical Code Technical Provisions 

ARTICLE 604 
Manufactured Wiring Systems 

SECTION 604.1 

Subsection 604.1(A) - Add a new subsection 604.1(A) to read as follows: 

(A) General. All such wiring systems shall be approved by the department, and shall comply with the 
installation requirements of this code in addition to the standards listed below. Each manufactured 
wiring system manufacturer shall add the following to its installation instructions: 

(1) With the electrical permit application for each installation, or any subsequent modification thereof, 
the licensed electrician shall include a diagram or specification sheet clearly defining the boundaries 
where the wiring method will be installed. 

(2) Manufactured wiring systems shall not be used for emergency exit signs or emergency lighting. 

(3) Such wiring shall be used only for general lighting circuits above an accessible hung ceiling or 
where no finished ceiling exists. 

SECTION 604.4 

Section 604.4 - Delete Exceptions No.l and No. 2 in their entirety. 

SECTION 604.6 

Subsection 604.6(A)(2) - Revise the first paragraph by inserting the word "metal" between "liquidtisht 
flexible" and "conduit." 



ARTICLE 605 

Office Furnishin gs (Consisting of Lighting Accessories and Wired Partitions^ 

SECTION 605.4 

Section 605.4 - Revise to read as follows: 

605.4 Partition Interconnections. The electrical connection between partitions shall be flexible 
assemblies listed and approved for use with wired partitions or metallic raceways that do not exceed 
610mm (2 ft) in length. 



66 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 6003 through Section 695.14 

SECTION 605.6 

Section 605.6 - Revise to read as follows: 

605.6 Fixed-Type and Freestanding-Type Partitions. Wired partitions that are fixed (secured to 
building surfaces) or freestanding (not fixed) shall be permanently connected to the building electrical 
system by one of the wiring methods of this code. Where liquidtight flexible metal conduit is used, the 
maximum length shall be 457mm (18 in.). 

SECTION 605.7 

Section 605.7 - Delete the section in its entirety. 

SECTION 605.8 

Section 605.8 - Delete the section in its entirety. 

ARTICLE 620 

Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and 

Stairway Chairlifts 

SECTION 620.12 

Subsection 620.12(B) - Revise to read as follows: 

(B) Other Wiring. All signaling and operating control circuits shall be minimum 24 AWG copper. 

SECTION 620.21 

Section 620.21 - Delete the words "rigid nonmetallic conduit" and "liquidtight flexible nonmetallic 
conduit" throughout. 

Subsection 620.21(A)(1)(d) - Delete paragraphs (d)(3) and (d)(4) in their entirety. 

Subsection 620.2 1 (A)(2)(d) - Delete paragraphs (d)(3) and (d)(4) in their entirety. 

Subsection 620.21(A)(3)(e) - Delete the subsection in its entirety. 

Subsection 620.21(A)(4) - Delete the subsection in its entirety. 

SECTION 620.23 

Subsection 620.23(C) - Insert the words "with ground-fault circuit interrupter" between "duplex 
receptacle" and "shall be provided." 



New York City 2011 Electrical Code 67 



Section 600.3 through Section 695.14 NYC 2011 Electrical Code Technical Provisions 

SECTION 620.24 

Subsection 620.24(A) - Revise the second sentence to read as follows: 

Required lighting and/or sump pump shall not be connected to the load side of a ground-fault circuit 
interrupter. 

F PN - replace "2004" with "2003 ." 

SECTION 620.61 

Section 620.61 - Add a second sentence to read as follows: 

For multiple elevators connected to the same feeder, each elevator circuit must be properly protected. 

SECTION 620.82 

Section 620.82 - Insert the words "including all door panels" between "metal enclosures" and "for all 
electrical equipment." 

ARTICLE 640 

Audio Signal Processing, Amplification, and Reproduction Equipment 

SECTION 640.3 

Subsection 640.3(J) - Delete the subsection in its entirety. 

ARTICLE 645 

Information Technology Equipment 

SECTION 645.17 

Subsection 645.17 - Delete the words: "each panelboard has no more than 42 overcurrent devices and" 

ARTICLE 668 
Electrolytic Cells 

SECTION 668.1 

Section 668.1 - Add a new paragraph at the end of the section to read as follows: 

No new electrolytic cell line shall be installed, nor any existing cell line modified, without special 
permission. 



6g New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 600.3 through Section 695.14 

ARTICLE 680 

Swimming Pools. Fountains, and Similar Installations 

SECTION 680.4 

Section 680.4 - At the end of the paragraph add the following: 

All applicable provisions of the New York City Construction Codes shall apply. 

SECTION 680.9 

Subsection 680.9 - At the end of the paragraph add the following: 

All such circuits shall be provided with GFPE. Electric water heaters of the immersion or submersible 
type shall not be permitted. 

SECTION 680.21 

Subsection 680.21(A)(3) - Revise by deleting the words "or liquidtight flexible nonmetallic conduit" 

SECTION 680.23 

Subsection 680.23(B)(1) - Revise the first sentence to read as follows: 

Listed and approved forming shells shall be installed for the mounting of all wet-niche underwater 
luminaires (fixtures) and shall be equipped with provisions for conduit entries. 

Subsection 680.23(B)(2) - Revise by deleting the words "liquidtight flexible nonmetallic" throughout. 

Subsection 680.23 (B)(2)(b) - Revise the first sentence to read as follows: 

Where a rigid nonmetallic conduit is used, an 8 AWG insulated solid or stranded copper equipment 
grounding conductor shall be installed in this conduit unless a listed low-voltage lighting system not 
requiring grounding is used. 

Subsection 680.23(D) - Revise to read as follows: 

(D) No-Niche Luminaires (Fixtures). A no-niche lighting fixture shall be supplied from a transformer 

meeting the requirements of 680.23(A)(2) and shall: 

(1) Have no exposed metal parts 

(2) Have an impact resistant polymeric lens and body, and 

(3) Be listed and approved for the purpose 

Subsection 680.23(F)(1) - Revise to read as follows: 

(1) Wiring Methods. Branch-circuit wiring on the supply side of enclosures and junction boxes 
connected to conduits run to wet-niche and no-niche luminaires (fixtures), and the field wiring 
compartments of dry-niche luminaires (fixtures), shall be installed using listed and approved rigid metal 
conduit, intermediate metal conduit, or rigid nonmetallic conduit. 

Exception: Electrical metallic tubing shall be permitted to be used to protect conductors, when installed 
within buildings. 



New York City 2011 Electrical Code 69 



Section 600.3 through Section 695.14 NYC 2011 Electrical Code Technical Provisions 

SECTION 680.33 

Section 680.33 - Revise to read as follows: 

680.33 Storable Pool Luminaires (Lighting Fixtures). Luminaires (lighting fixtures) for storable pools 
shall not be permitted. 

SECTION 680.41 

Section 680.41 - Revise section by deleting the last sentence. 

SECTION 680.42 

Subsection 680.42(A)(1) - Revise subsection by deleting the words "liquidtight flexible nonmetallic 
conduit" throughout. 

ARTICLE 682 

Natural and Artificially Made Bodies of Water 

SECTION 682.1 

Section 682.1 - Add the words "and water parks" at the end of the section. 

SECTION 682.2 

Section 682.2 - Add the words "and water parks" at the end of the first sentence of the definition of 
"Artificially Made Bodies of Water." 

SECTION 682.13 

Section 682.13 - In the first sentence delete the words "or liquidtight flexible nonmetallic conduit." 

ARTICLE 690 

Solar Photovoltaic Systems 

SECTION 690.1 

Section 690.1 - At the end of the section add the following: 

A detailed diagram of the photovoltaic system must be made available upon request of the department. 



70 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 600 J through Section 695.14 

ARTICLE 695 
Fire Pumps 

SECTION 695.1 

Subsection 695.1(A)(3) - Add a new subsection 695.1(A)(3) to read as follows: 
(3) Modification of existing fire pump power supply. 

SECTION 695.2 

Section 695.2 - After the first definition, "Fault Tolerant External Control Circuits," add two new 
definitions to read as follows: 

Fire Pump. For the purposes of this section, a fire pump is any Manual Standpipe Fire Pump, 
Automatic Standpipe Fire Pump, Sprinkler Booster Pump, Special Service Fire Pump, Spray Mist Fire 
Pump or Foam Fire Pump located at or below street level or with a motor rating exceeding 30hp. 

Limited Service Fire Pump. For the purposes of this section, a Limited Service Fire Pump is a fire 
pump located above street level with a motor rating not exceeding 30hp and connected to a limited 
service fire pump controller. 

Revise the third definition, "On-Site Standby Generator," to read as follows: 

On-Site Emergency Generator. An on-site facility producing electric power as the alternate supply of 
electric power meeting the requirements of Article 700. 

After the last definition, "On-Site Standby Generator," add a new definition to read as follows: 

Sprinkler Booster Pump. For the purposes of this section, a Sprinkler Booster Pump is a fire pump 
installed in J-2 occupancies, where a minimum of 5 psig is maintained at the highest line of sprinklers, 
that complies with the definition of Limited Service Fire Pump. 

SECTION 695.3 

Subsection 695.3(B) - Revise to read as follows: 

(B) Multiple Sources. Where required by the New York City Construction Codes, power from sources 
described in 695.3(A) shall be supplied from an approved combination of two or more such sources or 
an approved combination of one such source and an on-site emergency generator. The on-site 
emergency generator, complying with this section, shall be of sufficient capacity to allow normal 
starting and running of the motor(s) driving the fire pump(s) while supplying all other simultaneously 
operated loads. Optional standby loads shall be automatically shed when necessary to ensure the proper 
starting and operation of the fire pump. 

Subsection 695.3(C) - Add a new subsection 695.3(C) to read as follows: 

(O Multiple Independent Sources. Two or more feeder sources routed separately to the building and 
independently operated may be permitted for compliance with this section, as approved by the 
commissioner, where the reliability of the sources can be demonstrated. 



New York City 2011 Electrical Code 7 1 



Section 600.3 through Section 695.14 NYC 2011 Electrical Code Technical Provisions 

SECTION 695.4 

Section 695.4 - Revise to read as follows: 

695,4 Continuity of Power. Circuits that supply electric motor-driven fire pumps shall be supervised 
from inadvertent disconnection in accordance with (A) or (B) below. 

(A) General. Each utility and generator supply circuit that supplies an electric motor-driven fire pump 
or limited service fire pump shall be supplied from a single dedicated service disconnecting means and 
associated overcurrent protective device installed between the power source and one of the following: 

(1) A listed fire pump controller. 

(2) A listed fire pump power transfer switch. 

(3) A listed combination fire pump controller and power transfer switch. 

Exception 1: The service conductors may directly connect the power source to either the listed fire pump 
controller or combination fire pump controller and power transfer switch where available short circuit 
current is less than the rating of the fire pump controller or combination fire pump controller and power 
transfer switch. 

Exception 2: Where a limited service fire pump is connected to an emergency generator in addition to 
the electric utility source, the disconnecting means for either source is not required to be a service 
disconnecting means. 

Exception 3: Where the building service disconnecting means consists of multiple utility sources over 
600 volts arranged through transformers to supply a network secondary, a disconnecting means 
connected to the network complies with the requirements of this section. 

(B) Disconnecting Means and Overcurrent Protection. 

(1) Utility Service. Fire pumps and limited service fire pumps shall have overcurrent protection 
selected as to allow the operation of the fire pump for as long as the fire pump remains capable of 
running, except where direct connection is made in accordance with 695.4(A)(3) Exception 1: 

(1) Fire Pump. Fire pump overcurrent protection shall be selected at between 300 percent and 
600 percent of motor full load current. 

(2) Limited Service Fire Pump. Limited service fire pumps shall be protected by overcurrent 
devices selected at 150 percent of motor full load current. The next larger available device size 
may be used where selection results in a non-standard device size. 

(3) Disconnecting means shall be listed to accept the selected overcurrent device with no 
modification. 

(2) Generator Supply. When required to be connected to an emergency generator, fire pumps and 
limited service fire pumps shall have overcurrent protection selected in accordance with the following, 
except where direct connection is made in accordance with 695.4(A)(3) Exception 1: 

(1) Fire Pump. Fire pumps shall be protected by an over current device selected at not less than 
150 percent and not more than 300 percent of motor full load current. 

(2) Limited Service Fire Pump. Limited service fire pumps shall be protected by an overcurrent 
device selected at 150 percent of motor full load current. The next larger available size may be 
used where selection results in a non-standard size. 



72 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 600.3 through Section 695.14 

(3) Disconnecting means shall be listed to accept the selected fuse or circuit breaker trip with no 
modification. 

(4) A tap ahead of the on-site emergency generator disconnecting means shall be required for 
the fire pumps. 

Exception: Where multiple generators operate in parallel, the fire pump tap may be made on the 

parallel distribution bus. 

(3) Disconnecting Means. The disconnecting means shall comply with the following: 

(1) Be identified as suitable for use as service equipment. 

(2) Be lockable in the closed position. Locking provisions shall remain in place with or without 
an installed lock. 

(3) Not located within equipment that feeds loads other than the fire pump. 

(4) Be located as remote as practicable from other service disconnecting means with a minimum 
separation of 305mm (12 in.). 

Exception: (1), (3), and (4) shall not apply to fire pumps and limited service fire pumps connected to 
emergency generators. 

(S\ Disconnect Marking The disconnecting means shall be marked "Fire Pnmp - Do Not Disconnect 
Se lenel shah be aflea 6 ;, 25mm (1 in.) in height, and ftey shall be visible without opemng enclosure 
doors. Disconnecting means shall be red in color. 

(5) Controller Marking. A placard shall be placed adjacent to the fire pump 

controller stating overcurrent setting at 300 percent of motor full load current the location of the 
dSTonnecting means, and the location of the key (if the disconnecting means is locked). 

(6) Supervision. The power continuity shall be supervised by one of the following: 

(1) Central station signals confirming power source availability and pump running where central 
station connection is provided as required by building occupancy or use. 

(2) Local signaling device, audible and visual, for power source availability and pump running 
whichTaSedlt a continuously attended location where central station connection is not 
otherwise required. 

SECTION 695.5 

Section 695.5 - Revise to read as follows: 

695.5 Accessory Equipment. 

,A^ Transformers Where the service or system voltage is different from the utilization voltage of the 

following. 

m Size Transformers shall be rated at a minimum of 125 percent of the sum of the fire pump motors) 

and p« maintenance pump(s) motor loads, and 100 percent of the — ng load supphed by the 

transformer. 



New York City 2011 Electrical Code 



73 



Section 600.3 through Section 695.14 NYC 2011 Electrical Code Technical Provisions 

(2) Overcurrent Protection. Primary disconnecting means and overcurrent devices shall be selected in 
Te^ttT 695 - 4(BX1) - SeC ° ndary disCOnneCtin g means "* -ercurrent devices shall not be 

(3) Feeder Source. The feeders on the primary and secondary of the transformer shall be sized in 
accordance with the requirements of 695.6 adjusted for the primary and secondary voltage. 

(B) Utility Meters. Metering of fire pumps shall be current transformer driven or bypass type such that 
meter removal will not interrupt service to the fire pump. Metering may be dedicated to the fire pump or 
coincident wrth other building power use. F p 

toeVoltowh 1 ""' ReCtifierS may bC US6d t0 SUpply existin § DC fire P um P installation in accordance with 

(1) Size. Where a rectifier supplies an existing DC electric fire pump, it shall be rated at a minimum of 
125 percent of the fire pump full load current plus 100 percent of the full load current of all other 
equipment connected to the rectifier. 

Exception: If largest motor is other than the fire pump, rectifier shall be sized at 125 percent of the 
largest motor and 100 percent of all other equipment. J 

il?nTnf^ en ^ P ^ r0te fi C n , n • ?* Primaiy disconnectin S me *™ ^ overcurrent device shall be rated at 150 
percent of the rectfier full load current. The DC fire pump shall be supplied by a dedicated connection on the 
secondary of the rectifier. Disconnecting means and overcurrent devices shall not be permitted. 

(3) Feeder Source The feeders on the primary and secondary of the rectifier shall be sized in accordance with 
the requirements of 695.6 adjusted for the primary and secondary voltage. 

(4) Other Loads. Rectifiers installed to supply existing DC fire pumps shall be permitted to supply other 
loads. Rectifier capacity shall be increased in accordance with 695.5(C)(1). Each DC supply ZK 
disconnecting means and overcurrent device sized in accordance with applicable sections of L code. 

SECTION 695.fi 

Section 695.6 - Revise to read as follows: 

<o1t^°7 r W w£f P T er drCUitS 3nd Wiring meth0ds sha11 com P ! y with the requirements in 

m^SSf^awi" Pen * itted " m90(A) ' Exception 4; 230 - 94 ' Exception 4 ; 230 - 2 °£ 

^7 pl t y .^ 0nd " ff ?: S ' F A £ P T P ^ Hmited ServiC£ fire P um P su PP!y inductors shall be physically 
outed outside a building s) and shall be installed as service entrance conductors. Where supply 
conductors cannot be physically routed outside buildings, routing through buildings is permitted where 
installed in accordance with Section 230.6(1), (2), (4) or (5). ^ 

Exception: The supply conductors located in the electrical service room and generator room where thev 

firfr^Z!nT ePUmP " ^ "" * ***** * **" *° ^ ^^ ^~ ^ 
(B) Circuit Conductors. 

(1) Fire Pumps Fire pump supply conductors, including emergency supply conductors where 

3T7 T% 1S 1 Pr0V J ded ' ° n the l0ad Side ° f the final disconnectmg means and o^ent dev ce 
shall be kept entirely independent of all other wiring. They shall supply only loads thatTe direc^ 



74 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 600.3 through Section 695.14 

associated with the fire pump system, and shall be protected to resist potential damage by fire, structural 
failure, or operational damage. They shall be permitted to be routed through a building(s) using one ot 
the following methods: 

(1) Encased in a minimum of 50mm (2 in.) concrete using rigid metal conduit (steel RMC), 
intermediate metal conduit, electrical metallic tubing or schedule 80 non-metallic conduit. 

(2) Rigid metal conduit (steel RMC) within an enclosed construction dedicated to the fire pump 
circuit(s) having a minimum of a 2-hour fire resistance rating. 

(3) A listed electrical circuit protective system with a minimum 2-hour fire resistance rating. The 
installation shall comply with any restrictions provided in the listing of the electrical circuit 
protective system. 

Exception- The supply conductors located in the electrical service room and generator room where they 

originate and in the fire pump room shall not be required to have the minimum 2-hour fire separation or 

fire resistive rating. 

(2) Limited Service Fire Pumps. Limited service fire pump supply conductors shall be installed in rigid 

metal conduit (steel RMC) or intermediate metal conduit (steel IMC). 

Exception: Where there are multiple sources of supply with means of automatic transfer from one 

source to the other, electrical metallic tubing (EMT) shall also be permitted. 

(C\ Conductor Size. Conductors supplying a fire pump or a limited service fire pump shall have a 

rating not less than 125 percent of the full load current of the pump motor selected at no greater than 75 

degrees operating temperature of the conductor type used. 

<m Overload Protection. See 695.5(C)(2) for overload protection requirements. 

(Y?> Pump Wiring. All wiring from the controllers to the pump motors shall be in rigid metal conduit 

(steel RMC) or have a minimum 1-hour fire separation or fire resistance rating. 

Exception No. 1: Liquidtight flexible metal conduit (maximum of 915mm (36 in.)) is permitted for final 

connection to motor terminal housing. 

Exception No. 2: Intermediate metal conduit (steel IMC) and electrical metallic tubing (EMT) shall be 

permitted for limited service fire pumps. 

SECTION 695.10 

Section 695.10 - Revise to read as follows: 

695.10 Listed Equipment. Diesel engine driven fire pump controllers, electric fire pump controllers 
electric motors, fire pump transfer switches, foam pump controllers, and limited service controllers shall 
be listed and approved for fire pump use. 



New York City 2011 Electrical Code 



75 



Section 600.3 through Section 695.14 NYC 2011 Electrical Code Technical Provisions 

SECTION 695.1 4 

Subsection 695.14(E) - Revise to read as follows: 

, (E) Electric Fire Pump Control Wiring Methods. All electric motor driven fire pump control wiring 
sna 1 be in rigid metal conduit, intermediate metal conduit, liquidtight flexible metal conduit or Type MI 
cable. /F 

Exception: Electrical metallic tubing (EMI) shall be permitted for limited service fire pump control wiring. 
Subsection 695.14(F) - Add an Exception to read as follows: 

Exception: Electrical metallic tubing shall be permitted for limited service fire pump control wiring 
where provided with emergency generator supply. 



76 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 700 J through Section 770.154 

CHAPTER 7 
SPECIAL CONDITIONS 

ARTICLE 700 
Emergency Systems 

SECTION 700.1 

Section 700.1 - Delete FPN Nos. 2, 3, 4 and 5 and revise second sentence to read as follows: 

Emergency systems are lighting, fire protection and power systems legally required and classed as 
emergency by any governmental agency having jurisdiction. 

SECTION 700.4 

Subsection 700.4(A) - Revise to read as follows: 

(A) Acceptance Test. A licensed professional shall submit to the department a testing report of the 
completed system upon installation from an authorized testing entity. 

Subsection 700.4(E) - Revise to read as follows: 

(E) Installation Test Requirements. The installation test shall be conducted and documented in 
accordance with NFPA 1 10-2005, Section 7-13, amended as follows: 

7.13.3: Delete in its entirety. 

7.13.4.1(5): Add at the end of (5): Time to initial load transfer shall not exceed 10 seconds. 

7.13.4.1(11): Revise to read as follows: The load test with building load or other loads that simulate 
intended load shall continue for 2 hours observing and recording load changes and the resultant effect on 
voltage and frequency. 

7.13.10.2: Delete and replace with the following: The complete crank/rest cycle shall consist of 3-15 
second crank cycles with 15 second rest periods between cranks. 

7.13.13: Add a new paragraph to read as follows: Transfer switches shall be tested in accordance with 
8.4.6 as modified herein. 

Subsection 700.4(F) - Add a new subsection 700.4(F) to read as follows: 

(F) Maintenance and Operational Testing. Maintenance and operational testing shall be performed 
and documented in accordance with NFPA 1 10-2005, Section 8, amended as follows: 

8. 1 .2: Delete in its entirety. 

8.2: Delete in its entirety. 

8.3.1 : Delete the following text from the end: " . . .for the type and for the time duration specified for the class." 



New York City 2011 Electrical Code 11 



Section 700.1 through Section 770.154 NYC 2011 Electrical Code Technical Provisions 

8.3.4: Delete and replace with the following: A written record of the EPSS inspection, tests, exercising, 
operation, and repairs shall be maintained on premises and made available to the department on request. 
Records shall be inclusive of the transfer switches and storage batteries. 

8.4.4.1: Add a new sentence to read as follows: Inspection shall consist of examination of all EPSS 
components for leaks, abnormal device position and of all alarm/trouble indicators. 

8.4.5: Delete in its entirety. 

8.4.6: Replace "monthly" with "semi-annually." 

8.4.6.1: Replace "monthly" with "semi-annually." 

SECTION 700.5 

Subsection 700.5 (B) - Delete third paragraph of subsection 700.5(B), revise the first paragraph of such 
subsection and add a FPN to read as follows: 

The alternate power source shall be permitted to supply emergency and optional standby system loads 
where the source has adequate capacity or where automatic selective load pickup and load shedding is 
provided as needed to ensure adequate power to (1) emergency circuits and (2) optional standby circuits, 
in that order of priority. The alternate power source shall be permitted for peak load shaving, provided 
the above conditions are met. 

FPN: Peak reduction program may require utility approval 



SECTION 700.6 

Subsection 700.6 (E) - Add a new subsection 700.6(E) to read as follows: 

(E) Mechanical Operation. Means shall be provided to mechanically operate the switch without 
hazard to personnel. 

Subsection 700.6 (F) - Add a new subsection 700.6(F) to read as follows: 

(F) Temporary Connections for Portable Generators. Temporary connection of a portable generator 
without transfer equipment shall be permitted where qualified persons maintain and supervise service of 
the installation and where the normal supply is physically isolated by a lockable disconnect means or by 
disconnection of the normal supply conductors. Portable generators shall not be paralleled except by 
special permission. 

Subsection 700.6 (G) - Add a new subsection 700.6(G) to read as follows: 

(G) Permanent Connections for Portable Generators. Where a permanent installation is made for a 
portable generator, a disconnecting means and overcurrent protection shall be provided at the point of 
connection for the portable generator. Capacity shall not exceed the capacity of the permanent 
installation. 



78 New York City 201 1 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 700.1 through Section 770.154 

SECTION 700.7 

Section 700.7 - Revise to read as follows: 

Audible and visual signal devices shall be provided at a continuously supervised location for the 

following purposes: 

SECTION 700.9 

Subsection 700.9(A) - At the end of the subsection add the following: 

All accessible raceways, boxes and enclosures (including transfer switches, generators and power 

P.Lh)fo emergency circuits shall be permanently marked so they will be readily identified as a 

component of an emergency circuit or system. Accessible raceways shall be marked at least once every 

3 m (10 'ft) Acceptable means of marking shall include, but is not limited to, a permanently affixed 

identification nameplate, yellow in color with black lettering. 

Subsection 700.9(B) - Revise Exception to (5)(b) to read as follows: 

Exception to (5)(b): Overcurrent protection shall be permitted at the source for the equipment, provided 

feZZulVent protection is selectively coordinated in the overcurrent range with the downstream 

overcurrent protection. 

SECTION 700.10 

Section 700.10 - Add a new section 700.10 to read as follows: 

700.10 Conductors for Emergency Circuits. 

(M Ampacity. See 445.13. 

f m Tn^llation of G^^tnr Conductors. Generator conductors shall be installed in accordance with 

the requirements of Article 230. 

^ Overrent Devices. There shall be no limit to the number of overcurrent devices connected to 

the generator terminal devices. 

(BS W~ System Pumps. Fire system pumps or fire protection pumps requiring connection directly to 

^\rr g e^r g enerator as defined in the New York City Construction Codes shall be connected as 

follows: 

(1) Circuits supplying fire system pumps shall be connected directly to the emergency generator with 
oX ^ne o«n. 8 pro K cL device which shall be rated at not less man 150 percent and no. more 
than 600 percent of the pump full load current. 

Exception- Limited service fire pumps shall be protected by an overcurrent device selected at 150 
^S^f^Jua load current. The next largest available device size may be used where selection 
results in a non-standard device size. 

(2) Where multiple generators are paralleled, the connection for the fire system pumps shall be taken 
from the generator paralleling bus. 

Exception: Limited service fire pumps are not required to be directly connected to the emergency 
generator and may have additional overcurrent protective devices. 



New York City 2011 Electrical Code 



79 



Section 700.1 through Section 770.154 NYC 2011 Electrical Code Technical Provisions 

(3) Conductors and transformers feeding the system shall be sized at 125 percent of the pump full load current. 

(4) Separate circuits shall be used for each fire system pump. 

(E l A u art ?u S ? em ^ A11 buildin S" wide fire aIa ™ systems shall be provided with a dedicated transfer 
switch and be directly connected to the emergency generator overcurrent protective devices as follows: 

(1) 208/1 20V systems-by a dedicated fused disconnecting means. 

(2) 460/265V systems-by a dedicated fused disconnecting means with fused disconnecting means on the 
secondary of the associated transformer. 5 

SECTION 700. 12 

Section 700. 12 - Revise the fourth paragraph, add a new Exception to read as follows and delete the FPNs: 
Fire, sprinkler standpipe smoke detection, oxygen, nitrous oxide and other alarm or extinguishing 
prSion C ° t0 lhe Slde ° f * e SCrViCe 6qUipment and ShaU have Se P arate overcurreJ 

E arlTpme«et ^ i " Stattedfar hcal area Paction only, may connect ahead of the supply to the 
Subsection 700. 12(A) - Revise the first paragraph and add a FPN to read as follows: 

s S u2 e e SrT^ ^/T 1 ^ Y 01 ^ 6 ° f P ° Wer f ° r emergenC y U &ti°S s y stems ™* shall be of 
suitable rating and capacity to supply and maintain the total load for a minimum period of l'/ 2 hours 

SSt !■ r 1 " ^ ^ d t0 the ^ falHng bd0W 8VA perCent 0f noiTOaL Stor 4 batteries may be 
used for other emergency systems only where special permission is granted for such use. 

FPN: See Article 760 for additional information on the use of batteries for fire alarm systems. 
Subsection 700. 12(B)(2) - Revise first sentence and add a FPN to read as follows: 

Where internal combustion engines are used as the prime mover, an on-site fuel supply shall be provided 
sufficient for not less than 6 hours of operation at full demand load. proviaea 

FPN: Some installations may require more than 6 hours of fuel supply. See Articles 517 and 708. 
Subsection 700.12(B)(6) - Revise to read as follows: 

(6) Outdoor Generator Sets. Where an outdoor generator set is permanently installed and is equipped 
with a disconnecting means and such generator set is located within sight of the building or sSture 
tH PP I l a \ add T nal disCOnnectin S mean * ^all not be required where ungrounded cLucto™ 
through the building or structure. Appropriate signage shall be provided at the gener^dSltT 
first disconnecting means within the building or structure supplied. 

Subsection 700.12(B)(7) - Add new subsection 700.12(B)(7) to read as follows: 

(7) Temporary Generators. The equipment grounding conductor(s) of the derived svstem shall he 
bonded to the grounding electrode system. Y H be 

FPN: See 250.34 for grounding of generator frame. 

(a) Separately Derived System. Where a temporary portable generator is a separately derived 
system, it shall be grounded in accordance with 250.30. uenvea 



80 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 700 J through Section 770.154 

(b) Not A Separately Derived System. Where a temporary portable generator is not a separately 
derived system, a grounding connection shall not be made to the grounded circuit conductor. 

Subsection 700.12(C) - Revise to read as follows: 

(C) Uninterruptible Power Supplies, Uninterruptible power supplies may be used to provide power 
for emergency systems only where special permission is granted for such use. 

Subsection 700.12(D) - Revise the first sentence of subsection to read as follows: 

Where acceptable to the commissioner as suitable for use as an emergency source, a second service 
independent of the source normally supplying the building shall be permitted. 

Subsection 700.12(E) - Delete the subsection in its entirety. 

SECTION 700.26 

Section 700.26 - Revise to read as follows: 

700.26 Ground Fault Protection of Equipment. The alternate source for emergency systems shall not 
be permitted to have ground fault protection for equipment with automatic disconnecting means. Ground 
fault indication of the emergency source shall be provided pursuant to 700.7(D). 

SECTION 700.27 

Section 700.27 - Revise to read as follows: 

700.27 Coordination. Emergency system(s) overcurrent devices shall be selectively coordinated in the 
overcurrent range with all supply side overcurrent protective devices. 



SECTION 700.30 

Section 700.30 - Add a new section 700.30 under a new part "VII Grounding" to read as follows: 
VII. Grounding 

700.30 General. Grounding shall be in accordance with the provisions of Article 250. 

SECTION 700.31 

Section 700.31 -Add a new section 700.31 to read as follows: 

700.31 Control Circuits. 

(A) Grounding. Low voltage control circuits and DC control circuits derived from engine generator 
starting batteries shall have one leg grounded. 

(B) Arrangements. Control circuits shall be arranged so that an additional accidental ground shall not 
cause operation of the connected devices. 

(O Return Path. Control circuits shall not make use of the equipment grounding conductor as a circuit 
path. 



New York City 2011 Electrical Code 81 



Section 700.1 through Section 770.154 NYC 2011 Electrical Code Technical Provisions 

ARTICLE 701 

Legally Required Standby Systems 



ARTICLE 701 

Legally Required Standby Systems. Delete the article in its entirety and add a FPN to read as follows: 
FPN: All legally required standby systems are classified as emergency systems. 

ARTICLE 702 

Optional Standby Systems 

SECTION 702.6 

Section 702.6 - At the Exception, add a second sentence to read as follows: 

Portable generators shall not be paralleled with permanent optional standby sources, except by special 
permission. 

SECTION 702.12 

Section 702.12 - Add a new section 702.12 to read as follows: 

702.12 Portable and Temporary Generators. Portable and temporary generators shall comply with 
700.6(G) and 700.12(B)(7). 

ARTICLE 705 

Interconnected Electric Power Production Sources 

SECTION 705.40 

Section 705.40 - Add a new paragraph after the first paragraph to read as follows: 

Special detection methods shall be required to determine that a primary source supply system outage has 
occurred, and whether there should be automatic disconnection. When the primary source supply is 
restored, special detection methods shall be required to limit exposure of power production to out-of- 
phase reconnection. 

Delete the Exception in its entirety. 

Delete FPN No.l in its entirety. 



82 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 700.1 throughJ ectionTTOAU 

SFCTTON 705.42 

Section 705.42 - Delete the words "or legally required standby" from the last sentence and delete the 
Exception in its entirety. 

ARTTCLE 708 

Critic al O peration s Pnwer Systems (COPS) 

ATJTTf^T J? 708 

Critical Operations Porrer Systems (COPS). Re-designate FPN as FPN No.2 and add FPN No.l to 

read as follows: . 

FPN No.1: Determination of a Designated Critica. Operations Area (DCOA ) an the Cnttca 
Operas Power Systems (COPS, ^™%^&^'$£%ZZ 
t^^^^^X^SX^ * ■***» strawy and determine 
compliance with the requirements of this article. 

ARTTCLE 725 

^*« i , rw 7, and Class * ^^nf P -Cnntrol Stalin?, and Power- 
Tim ited Circuits 



SECTION 725 2 

Section 725.2 -Revise the first definition, "Abandoned Cass 2, Class 3, and PLTC Cable" and FPN as 

of the opposing end. 

FPN Replace "725.21" with "725.41 ." 

SFCTTON 725.3 

Subsection 725.3(C) -Revise the Exception to read as follows: 

**,*»■ 2fe» CZ2P ., ^ CXP3P cables shall be P^fc™?*™* °™ ' ^ 
Stalled in other spaces used for environmental air in accordance wtffe 725.154(A). 



83 



New York City 2011 Electrical Code 



Section 700.1 through Section 770.154 Nvronnvi >• ,^ J „ 

1 I NYC 2011 Electrical Code Technical P rovisions 

SECTION 725.74 

Section 725.24 - Revise the third sentence and add a new FPN to read as follows- 

SECTION 725 .7.5 

Section 725.25 - Revise the title to read as follows: 

Abandoned Cables, Power Sources and Oth.r A ^ ^ted F^ p-.,* 

Add an additional sentence at the end of the paragraph to read as follows- 

SECTION 725 177 

Section 725.127 - Revise the Exception by replacing "14 AWG" with "12 AWG." 

SECTION 72* .nn 

Section 725.130(A) - Delete Exception No. 2 and the FPN in their entirety. 

SECTION 72* 1M 

Section 725. 136 - Delete the words "non-power limited fire alarm" 
Subsection 725.136(B) - Delete the words "non-power limited fire alarm- 
Subsection 725.136(C) - Delete the words "non-power limited fire alarm- 
Subsection 725.136(D) - Delete the words "non-power limited fire alarm" 

S££L^$° - Ddete ^ ^ "^ "< W and "lionidtight flexible 

SECTION 725 /no 

Section 725.139(E)(1) - Delete the subsection in its entirety. 



84 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 700.1 through Section 770.154 

SECTION 725.154 

Section 725.154(A) - Revise the title and first and second sentences to read as follows: 

(A) Spaces Used For Environmental Air. Cables installed in spaces used for environmental air shall be 
Class CL2P or CL3P. Cables shall not be installed in ducts or plenums. 

ARTICLE 727 

Instrumentation Trav Cable: Type ITC 

SECTION 727.4 

Section 727.4 - Revise to read as follows: 

727.4 Uses Permitted. Where approved, Type ITC cable shall be permitted to be used as follows in 
industrial establishments where conditions of maintenance and supervision ensure that only qualified 
persons will service the installation: 

(1) In cable trays. 

(2) In raceways. 

(3) In hazardous locations as permitted in 501.10, 502.10, 503.10, 504.20, 504.30, 504.80 and 505.15. 

(4) Enclosed in a smooth metallic sheath, continuous corrugated metallic sheath, or interlocking tape 
armor applied over the nonmetallic sheath in accordance with 727.6. The cable shall be supported and 
secured at intervals not exceeding 1.83m (6 ft). 

(5) Between cable tray and equipment in lengths not to exceed 7.62 m (25 ft), where the cable complies 
with the crush and impact requirements of Type MC cable and is identified for such use. The cable shall 
be supported and secured at intervals not exceeding 1.83m (6 ft). 

ARTICLE 760 
Fire Alarm Systems 

SECTION 760.1 

Section 760.1 - Revise FPN No. 1 by deleting the words "guard's tour," in first sentence and 
revise the last sentence to read as follows: 

For further information on the installation and monitoring of integrity requirements for fire alarm 
systems, refer to NFPA 72, National Fire Alarm Code, 2002 edition. 

Add a new FPN No. 3 to read as follows: 

FPN No. 3: See Section BC 907 of the NYC Building Code for components description and use. 



New York City 2011 Electrical Code 85 



Section 700.1 through Section 770.154 NYC 2011 Electrical Code Technical Provisions 

SECTION 760.2 

Section 760.2 - At the end of the definition of "Abandoned Fire Alarm Cable" add the following words: 
"However, a tag shall be securely fixed to each end indicating location of opposing end." 

SECTION 760.3 

Subsection 760.3(B) - Delete the subsection in its entirety. 
Subsection 760.3(F) - Revise to read as follows: 

(F) Optical Fiber Cables. Where optical fiber cables are utilized for fire alarm circuits, the cables shall 
be supervised and installed in raceway per Articles 342, 344 or 358 in accordance with Article 770 and 
terminated in equipment listed for fire alarm use. 

Subsection 760.3(G) - Revise to read as follows: 

(G) Installations of Conductors with Other Systems. Installations shall comply with 300.8 and 
760.136. 



SECTION 760.24 

Section 760.24 - Add the following words at the end of the paragraph: "Raceways, where installed shall 
be minimum 1.9cm (3/4 in.) trade size. See 760.52 and 760.131 for installations requiring raceways." 

SECTION 760.25 

Section 760.25 - Add the following words at the end of the paragraph: " ..and securely fixed to each end 
indicating location of opposing end." 

SECTION 760.32 

Section 760.32 - Revise to read as follows: 

760.32 Fire Alarm Circuits Extending Beyond One Building. Power-limited fire alarm circuits that 
extend beyond one building and run outdoors shall be installed in raceway in accordance with Articles 
342 or 344. Non-power limited fire alarm circuits that extend beyond one building and run outdoors 
shall meet the installation requirements of Part 1 of Article 300 and the applicable sections of Part 1 of 
Article 225 and shall be installed in raceway in accordance with Article 342 or 344. 



86 New York City 201 1 Electrical Code 



NYC 2 011 Electrical Code Technical Provisions Section 700.1 through Section 770.154 

SF.CTTON 760.33 

Section 760.33 - Add a new section 760.33 to read as follows; 

760 33 Fire Alarm Circuit and Equipment Grounding. Fire alarm circuits and equipment shall be 

grounded in accordance with Article 250 and shall comply with the following requirements: 

( M Grounding Electrode Conductor. A grounding electrode conductor shall be sized and installed in 

accordance with Article 250, Table 250.66, using a minimum of 10 AWG, at the primary and secondary 

power source supplying the fire alarm system. 

fffl Fnuinment Grounding Conductor. A separate green insulated equipment grounding conductor shall 

be sized and installed in accordance with Article 250, Table 250.122, using a minimum of 10AWG, where 

there are conduits supplying 120V to the fire command center, control unit or distributed control cabinets. 

(C\ Crowding S p pwelv Thrived Supply. A green insulated equipment grounding conductor shall 

be sized and installed in accordance with Article 250, Table 250.122, using a minimum of 10 AWG, in 

distributed cabinets where the 120V supply is not derived from the main fire alarm power supply. In 

steel framed buildings, an additional connection to local steel shall be permitted. 

SECTION 760.41 

Section 760.41- Delete the section in its entirety and replace to read as follows: 

760.41 Power Source Requirements. The power source for fire alarm circuits shall comply with the 

following: 

f A) Primary Power Source. All fire alarm circuits shall be provided with a primary power source. The 

primary power source shall be generated electric power not exceeding 277/480 volts, supplied by utih y 

company power or isolated plant. The primary power supply to the fire alarm system shall comply with 

the following: 

(1) Primary Power Supply for the Fire Alarm System. Primary power supply for the fire alarm 
system shall be connected to the primary power source ahead of all building service disconnecting 
means so that the building service disconnecting means can be opened without de-energizing the fire 
alarm supply. All utility metering of the fire alarm system, including disabling or removal of meters, 
shall maintain power continuity to the fire alarm system at all times. 

(2) Limited Interior Fire Alarm Systems. Primary power supply for sub-systems or other limited 
interior fire alarm systems may be connected to the power supply through the protected area of such 
systems by means of a connection ahead of the disconnecting means for the power supply to the 
protected area. 

FPN: Sub-systems and limited interior fire alarm systems may also use the connected means 

defined in paragraph (1) where available. 
(B) Somndarv Power Source. Where an emergency power system is provided or required to be 
provided for emergency system loads, the fire alarm circuits shall be provided with a secondary power 
source Batteries shall not be a substitute for connection to a secondary power source The secondary 
power source shall comply with the requirements for emergency power systems and/or emergency 
generator that are used for emergency systems loads as articulated below: 



New York City 2011 Electrical Code 



87 



Section 700.1 through Section 770.154 NYC 2011 Electrical C ode Technical Provisions 

(1) Generally. Emergency power systems complying with Chapter 27 of the 2008 Building Code shall 
be permitted to serve as a secondary power source or 

(2) Existing Buildings. Emergency power systems and/or emergency generators in existing buildings in 
compliance with Title 27, chapter 1, subchapter 6, section 27-396.4 of the Administrative Code (also 
referred to as the 1968 Building Code) shall be permitted to serve as the secondary power source. 

The secondary power supply shall be connected such that all other disconnecting means serving other 
building emergency loads can be opened without de-energizing the facility fire alarm secondary power 
supply. 

FPN: The use of a main disconnecting means on the output of the generator(s) is permitted where 
the disconnection of all other loads does not interrupt the facility fire alarm system secondary 
power supply. 

(C) Battery. Regardless of whether a secondary power source is also provided, each fire alarm system 
and subsystem shall be equipped with a storage battery power supply sized to meet the operating power 
requirements of the system in accordance with (1), (2) or (3) below and shall automatically connect to 
and operate the fire alarm system upon failure of the primary or secondary power supply or sources. 
Batteries shall not be a substitute for connection to a secondary power source when a secondary power 
source is required pursuant to subsection (B) above. 

(1) With Voice Communications Capability. Supervisory operation for 24 hours followed by full load 
operation for 6 hours for systems with voice communications capability. 

FPN: A 45 minute period of voice and alarm operation at the maximum connected load shall be 
considered equivalent to 6 hours of total system operation. 

(2) Without Voice Communications Capability. Supervisory operation for 24 hours followed by full 
load operation for 15 minutes for systems without voice communications capability. 

(3) Sub-systems or Other Limited Interior Fire Alarm Systems. Supervisory operation for 24 hours 
followed by full load operation for 5 minutes for sub-systems or other limited interior fire alarm systems 
operating within a facility that reports to the overall facility fire alarm system. 

(D) Arrangement of Power Sources. One source of power shall be connected to the fire alarm system at all 
times. The primary and secondary power sources shall be arranged and controlled by automatic transfer 
switches dedicated to the fire alarm system such that the secondary source will be automatically connected to 
the fire alarm system should the primary power source fail. The following conditions shall be observed: 

(1) Intermediary devices between the fire alarm system power supply and the power source, other than 
fused disconnect switches, transformers and automatic transfer switches are prohibited. Such disconnect 
switches, transformers and automatic transfer switches shall supply only the fire alarm system and other 
systems specifically permitted by applicable New York City rules and regulations. 

(2) The primary and secondary power source shall each be provided with a means of disconnect from 
the fire alarm system. Each disconnect shall consist of a fused disconnect switch, locked in the ON 
position and the key shall be kept on premises and made accessible only to authorized personnel Such 
disconnect shall be painted red and permanently identified as a fire alarm circuit and labeled as to 
system/location served, with a means of interrupting the unfused grounded and all ungrounded 
conductors. 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 700.1 through Section 770.154 

(3) The fire alarm system fused disconnect switch on the transformer secondary side shall comply with the 
requirements of the primary and secondary power source fused disconnect switches pursuant to Article 240. 

(4) For buildings served at up to 300 volts to ground, the service voltage shall be transformed to 
208/120 volts and a fire alarm fuse disconnect provided within a circuit length often (10) feet, shall be 
connected at the transformer secondary on the 208/120 volt side. Fused cutouts shall be provided where 
multiple circuits are required to support the fire alarm system and related auxiliaries mounted in a fused 
cutout panel suitable for the number of circuits needed. 

SECTION 760.43 

Section 760.43 - Revise the first sentence by replacing "14 AWG" with "12 AWG" and delete the last 
sentence. 

SECTION 760.45 

Section 760.45 - Delete the Exceptions and the FPN in their entirety. 

SECTION 760.46 

Section 760.46 - Revise to read as follows: 

760.46 NPLFA Circuit Wiring. Installation of non-power limited fire alarm circuits shall be in accordance 
with applicable portions of 110.3(B), 300.7, 300.15, 300.17 and other appropriate articles of Chapter 3 using 
raceway methods described in 342 and 344 or use Type MI Cable in accordance with 332. 

Exception No. 1: As provided in 760.48 through 760.53. 

Exception No. 2: Where other articles of this Code require other methods. 

SECTION 760.48 

Subsection 760.48(A) - Revise to read as follows: 

(A) NPLFA Circuits. Non-power limited fire alarm circuit conductors shall not be permitted to occupy 
the same cable, enclosure or raceway with circuit conductors of other systems. 

Subsection 760.48(B) - Revise to read as follows: 

(B) Fire Alarm with Power-Supply Circuits. Power supply and fire alarm circuit conductors shall be 
permitted in the same enclosure only where connected to the same equipment. 

SECTION 760.49 

Subsection 760.49(A) - Revise to read as follows: 

(A) Sizes and Use. Only copper conductors size 12 AWG and larger shall be permitted to be used as 
NPLFA circuit conductors. 

Subsection 760.49(B) - Delete the FPN in its entirety and revise to read as follows: 



New York City 2011 Electrical Code 89 



Section 700 J through Section 770 J 54 NYC 2011 Electrical Code Technical Provisions 

(B) Insulation. Insulation on conductors shall be suitable for 600 volts, 90 degrees C, and shall comply 
with Article 310. Conductors shall be Type THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW2, 
XHH, XHHW, MI or CI-NYC Certified Cable. Application of conductor ampacity shall be in 
accordance with 1 10.14 for terminal device ratings. 

Subsection 760.49(C) - Revise to read as follows: 

(C) Conductor Materials. Conductors shall be solid copper up to size 10 AWG. Stranded copper 
conductors shall be used for sizes 8 AWG and larger. 

SECTION 760.51 

Subsection 760.5 1(A) - Delete the words "and Class 1 Circuits" in title and "and Class 1 circuit" in text. 

Subsection 760.51(B) - Delete the subsection in its entirety. 

Subsection 760.51(C) - Revise to read as follows: 

(O Cable Trays. Where non-power limited fire alarm circuit conductors are installed in cable trays, 
they shall comply with 392.9 through 392.11 and shall be barriered from any other wiring installed in 
the cable tray. 

SECTION 760.52 

Section 760.52 - Add a new section 760.52 to read as follows: 

760.52 Mechanical Execution of Work. Installation shall comply with the following: 

(A) Mechanical Rooms, Elevator Rooms, Garages and Loading Docks. All wiring installed up to 
2.4m (8 ft.) above the finished floor in garages, loading docks, mechanical rooms, and elevator rooms 
shall meet the installation requirements of Article 344. All wiring installed over 2.4m (8 ft.) above the 
finished floor shall meet the installation requirements of Articles 332, 342, 344 or 358. 

Exception: For mechanical rooms and elevator rooms having a floor area of less than 900 square feet, 
installation pursuant to Articles 332, 342, 344 or 358 is permitted without height limitation, 

(B) Installation. Installation of raceways, boxes, enclosures, cabinets and wiring shall conform to the 
following requirements: 

(1) Covers of boxes, enclosures and cabinets shall be painted red and permanently identified as to use. 

(2) Penetrations through rated walls, ceilings and floors shall be fire stopped. 

(3) Raceways or wiring shall not penetrate the top of any control equipment cabinet or enclosure. 

(4) Raceways installed up to 2.4m (8 ft.) in stairways shall not reduce or obstruct required stairway 
radius or egress path. 



90 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 700.1 through Section 770.154 

SECTION 760.53 

Section 760.53 - Delete the section in its entirety and replace to read as follows: 

760.53 Fire Alarm Circuit Integrity (CI) Cable. Cables suitable for use in fire alarm systems to ensure 
survivability of critical circuits during a specified time under fire conditions shall be listed as circuit integrity 
cable. Cables so identified shall have the classification "CI-NYC certified fire alarm cable." 

SECTION 760.121 

Subsection 760.121(A) - Delete FPN Nos. 1 and 2 in their entirety. 

SECTION 760.124 

Section 760.124 - Delete the FPN in its entirety. 

SECTION 760.127 

Section 760.127 - Delete the Exception in its entirety. 

SECTION 760.130 

Subsection 760.130(A) - Revise Exception No. 2 by adding "760.51" after "760.49," delete Exception 

No. 3 and delete the FPN in their entirety. 

Subsection 760.130(B) - Revise the last sentence to read as follows: 

Devices shall be installed in accordance with Sections 110.3(B), 300.11(A) and 300.15 with all wiring 

supported independently from the building structure. 

Subsection 760.130(B)(1) - Revise to read as follows: 

(1) Exposed or Fished in Concealed Spaces. In raceway or exposed above 2.4m (8 ft.) on the surface 
of ceiling and sidewalls or fished in concealed spaces, cable splices or terminations shall be made in 
listed fittings, boxes, enclosures, fire alarm devices or utilization equipment. Where installed exposed, 
cables shall be supported at a maximum of 1.5m (5 ft.) spacing and installed in such a way that 
maximum protection against physical damage is afforded by building construction. Where located 
within 2.4m (8 ft.) of the floor, cables shall be installed in raceway as per Article 342, 344, 358 or 386. 

Subsection 760.130(B)(2) - Revise to read as follows: 

(2) Passing Through a Floor or Wall. In metal raceways where passing through a floor or wall to a 
height of 2.4m ( 8 ft.) above the floor, unless adequate protection can be afforded by building 
construction as per 760.130(B)(1) or unless an equivalent solid guard is provided. 

FPN: Protection by building construction includes, but is not limited to, raised floors, shafts, telephone 
and communications equipment rooms and closets, and rooms used exclusively for fire alarm equipment. 

Subsection 760.130(B)(3) - Delete the words "rigid nonmetallic conduit,." 

Subsection 760.130(B)(4) - Add a new subsection 760.130(B)(4) to read as follows: 



New York City 2011 Electrical Code 9 * 



Section 700.1 through Section 770.154 NYC 2011 Electrical Code Technical Provisions 

(4) Terminations and Splices. Terminations and splices shall be made with terminal blocks and in 
listed fittings, boxes, enclosures, fire alarm devices or utilization equipment. Splices shall be limited to 
locations where the conditions of installation require the use of splices. Splices and terminations in riser 
cables are prohibited except where made in fire alarm equipment terminal cabinets. Conductors shall be 
mechanical connections listed in accordance with UL 486 (2003) A & C or if soldered, conductors shall 
first be joined so as to be mechanically and electrically secure prior to soldering. Temperature rating of 
completed splices shall be equal to or exceed the temperature rating of the highest rated conductor. 

SECTION 760.131 

Add a new section 760.131, to read as follows: 

760.131 Mechanical Execution of Work. Installation shall conform to the following requirements: 

(A) Mechanical Rooms , Elevator Rooms, Garages and Loading Docks. All wiring installed up to 2.4m 
(8 ft.) above the finished floor in garages, loading docks, mechanical rooms, and elevator rooms shall meet 
the installation requirements of Article 344. 

Exception: For mechanical rooms and elevator rooms having a floor area of less than 900 square feet 
installation pursuant to Articles 332, 342, 344 or 358 is permitted without height limitation. 

(B) Exting uishing Systems. Extinguishing and suppression systems activated by automatic fire detection 
and using fire alarm cables shall be installed pursuant to Articles 332, 342, 344 or 358. Such systems shall 
include, but not be limited to, pre-action sprinkler, deluge sprinkler, water mist, clean air agent, Halon, range 
hood, C0 2 , and dry chemicals. 

(C) Installation. Installation of raceways, boxes, enclosures, cabinets and wiring shall conform to the 
following requirements: 

(1) Covers of boxes, enclosures and cabinets shall be painted red and permanently identified as to use. 

(2) Penetrations through rated walls, ceilings and floors shall be fire stopped. 

(3) Raceways or wiring shall not penetrate the top of any control equipment cabinet or enclosure. 

(4) Raceways installed up to 2.4m (8 ft.) in stairways shall not reduce or obstruct required stairway 
radius or egress path. 

(5) Cables shall be secured by cable ties, straps or similar fittings designed and installed so as to not 
damage cables. Such fittings shall be secured in place at intervals not exceeding 1.5m (5 ft.) on center 
and within 0.3m (1 ft.) of associated cabinet, enclosure, or box. 

SECTION 760.136 

Subsection 760.136(D)(2)(a) - Replace "Type FPL, FPLR, FPLP or permitted substitute cables" with 
"type FPLP 'NYC certified fire alarm cable' or other NYC certified fire alarm cable." 

Subsection 760.136(D)(2)(b) - Delete the subsection in its entirety. 

Subsection 760.136(F) - From the first sentence, delete "rigid nonmetallic conduit" and "liquidtight 
flexible nonmetallic conduit." 



92 New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technical Provisions Section 700.1 through Section 770.154 

Subsection 760.136(G)(1)(b) - Revise to read as follows: 

(b) all of the power-limited fire alarm circuit conductors are in a raceway or metal-sheathed or metal- 

clad cables. 

SFCTTON 760.139 

Section 760.139 - Delete the section in its entirety. 

SFCTTON 760.142 

Section 760.142 - Revise to read as follows: 

760.142 Conductor Size. Conductors shall not be smaller than 18 AWG in size. 

SFCTTON 760.143 

Section 760.143 - Revise to read as follows: 

760 143 Support of Conductors. Power-limited fire alarm circuit conductors shall not be strapped 

ta^ed or 2che5 by any means to the exterior of any piping, duct, conduit, or raceway as a means of 

support. 

SFCTTON 760.154 

Subsection 760.154(A) - Revise to read as follows: 

environmental air, or where permitted to run exposed m other areas, shall be Type FPLP NYC Certitied 

Fire Alarm Cable." 

Subsection 760.154(B)(1) - Replace "Type FPLR" with "Type FPLP 'NYC Certified Fire Alarm Cable 

or other NYC Certified Fire Alarm Cable" in each of two locations. 

Subsection 760.154(B)(2) - At the beginning of the sentence, replace "Other cables" with "FPLP 'NYC 

Certified Fire Alarm Cable' ." 

Subsection 760.154(C) - Delete the subsection in its entirety and revise to read as follows: 

f r ,ww irinB Within Buildings . Cables installed in building locations other than those covered m 

760.154(A) or (B) shall be Type FPLP "NYC Certified Fire Alarm Cable. 

Subsection 760.154(D) - Revise the subsection to read as follows: 

r ) ^ A , Q ^r g h 1P Snhstitutions. Substitutions of Type FPLP "NYC Certified Fire Alarm Cable" 

or other NYC Certified Fire Alarm Cables shall not be permitted. 

Delete the Figure, Table and FPN in their entirety. 



New York City 2011 Electrical Code 



93 



Section 700.1 through Section 770.154 mC2011 Electrical Code Technical Provisions 



entirety. 



SECTION 760. 176 

Section 760. 1 76 (G) - Delete the first sentence of the first paragraph, the FPN and the Table in their 

SECTION 760.1 7Q 

Section 760. 179 - Revise the title to read as follows: 

LtrecIor^ iStinP *** ^^ ° f ?LFA ^'^ *"* T nsulated r ™ t; ""ous Line-Tvn. m rf > 

Subsection 760.179(B) - Revise to read as follows: 

fean^8AWG 0r ^ ^ ^ ° f C ° ndUCt ° rS in sin § le or multi-conductor cables shall not be smaller 

Subsection 760. 1 79(D) - Delete the FPN in its entirety and revise to read as follows: 

SL TV f e F p ?T ' P - ^ e F J PL I > .P ower - limited Are alarm cable shall be listed to UL1424-05, Standard for 

^:™^ d - Flre - Alan * CirCUkS ^ ^ *** -"* <» -P^ce with the r 

(1) Type FPLP only; minimum insulation thickness 15 mils; minimum temperature 150 C. 

(2) Red colored jacket overall; minimum thickness 25 mils. 

FIRf'aI'aTm.^ /mf-Y L if 4 T 1 bCar additi ° nal descri P tion "ALSO CLASSIFIED NYC CERT. 
riKh, ALARM CABLE, legible without removing jacket. 

Subsection 760.179(E) - Delete the subsection in its entirety. 

Subsection 760.179(F) - Delete the subsection in its entirety. 

Sa^^fS^^? b /r dele - in f " CI " fr ° m ^ &St S6ntenCe ° f the &st P"WPh and 

:^z:l of^s pr£ph Circmt Integnty Fire Aiam cabie "' ** deieting ^ ^ in ^ 

?^^to2£££? FPLP ' FPLR ' or FPL cable " at end of -™ ^ " T - 

Subsection 760.179(1) - Delete subsection 760.179(1) and add a new 760.179(1) to read as follows: 

(I) Cable Marking The cable shall be marked in accordance with subsection 760.179(D)(3) and its 
rating as NYC Cert. Fire Alarm Cable or NYC Cert. Circuit Integrity Cable. ^ 

Subsection 760. 179(J) -Delete "through (F)» in fourth line of the paragraph. 

Subsection 760.179(K) - Add new subsection 760.179(K) to read as follows: 

(K) Listed Fire-Rated Assemblies, MI cable meeting the requirements of Article 332 or listed fire 
rated assemblies that have a minimum fire rating of 2 hours shall be permitted wL iSedfo 
accordance with the listing requirements. F n mstalled in 



94 



New York City 2011 Electrical Code 



NYC 20 11 Electrical Code Technical Provisions Section 700.1 through Section 770.154 

ARTICLE 770 

Optical Fiber Cables and Raceways 

SECTION 770.2 

Section 770.2 - Revise the definition of "Abandoned Optical Fiber Cable" to read as follows: 
Abandoned Optical Fiber Cable. Installed optical fiber cable that is not terminated at equipment other 
than a connector and not identified for future use with a tag securely fixed to each end and indicating the 
location of the opposing end. 

SECTION 770.3 

Section 770.3 - Revise first sentence to read as follows: 

Circuits and equipment shall comply with 770.3(A), (B) and (C). 

Subsection 770.3(C) - Add a new subsection 770.3(C) to read as follows: 

(C\ Electric Closets. Fiber optic circuits and equipment shall not be installed in electric closets. 

SECTION 770.25 

Section 770.25 - Revise the title to read as follows: 

Abandoned Cables and Power Sources. 

Section 770 25 - Add a new third sentence to read as follows: Abandoned Power Sources and other 
associated equipment shall be removed. Power sources and other associated equipment not tagged for 
future use shall be de-energized. 

SECTION 770.48 

Subsection 770.48(A) - Add a new second sentence to subsection 770.48(A) to read as follows: All 

other cables shall be considered to be within the building. 

Subsection 770.48(B) - Delete the words "Article 352, Rigid Polyvinyl Chloride Conduit: Type PVC." 

SECTION 770.100 

Subsection 770.100(A)(3) - Revise the first sentence by replacing "14 AWG" with "12 AWG." 



New York City 2011 Electrical Code 



95 



Section 700.1 through Section 770.154 NYC 2011 Electrical Code Technical Pro visions 

SECTION 770.133 

Subsection 770.133(A) - Delete the words "non-power-limited fire alarm" throughout. 

Subsection 770.133(B)(2) - Delete the subsection in its entirety. 

Subsection 770.133(D) - Add a new subsection 770.133(D) to read as follows: 

(D) Electric Closets. Equipment and cabling shall not be installed in electric closets. 

SECTION 770.154 

Subsection 770.154(A) - Revise to read as follows: 

(A) Spaces Used for Environmental Air. Cables shall not be installed in ducts or plenums. Cables 
installed in spaces used for environmental air shall be Type OFNP or OFCP. Abandoned cables shall 
not be permitted to remain. Types OFNR, OFCR, OFNG, OFN, OFCG, and OFC cables installed in 
compliance with 300.22 shall be permitted. Listed plenum optical fiber raceways shall be permitted in 
spaces used to convey environmental air or as described in 300.22(c). Only Type OFNG, and OFCP 
cables shall be permitted to be installed in these raceways. 



96 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code T echnical Provisions Section 800.2 through Section 830.133 

Chapter 8 
Communications Systems 

ARTICLE 800 
Communications Circuits 

SECTION 800.2 

Section 800.2 - Revise the definition of "Abandoned Communications Cable" to read as follows: 
Abandoned Communications Cable. Installed communications cable that is not terminated at both 
ends at a connector or other equipment and not identified for future use with a tag securely fixed to each 
end and indicating the location of the opposing end. 

SECTION 800.24 

Section 800.24 - Revise the second sentence to read as follows: 

Cables installed exposed on the surface of ceilings and sidewalls shall be supported by the building 

structure in such a manner that the cable will not be damaged by normal building use or present a safety 

hazard. 

SECTION 800.25 

Section 800.25 - Revise the title and first sentence to read as follows: 

800 25 Abandoned Cables, Power Sources & Other Associated Equipment. The accessible portion 
of abandoned communications cables, power sources and other special equipment shall be removed. 
Cables, power sources and other special equipment not tagged for future use shall be de-energized. 

SECTION 800.100 

Subsection 800.100(A)(3) - Replace "14 AWG" with "12 AWG." 



New York City 2011 Electrical Code 



97 



Section 800.2 through Section 830.133 NYC 2011 Electrical Code Technical Provisions 

SECTION 800.133 

Section 800.133 - Revise to read as follows: 

800.133 Communications wires, cables and equipment inside of buildings shall not be installed in 
electric closets and shall comply with 800.133(A) through (D). 

Subsection 800.133(D) - Add a new subsection 800.133(D) to read as follows: 

(D) Electric Closets. Communications equipment and cabling shall not be installed in Electric Closets. 

SECTION 800.154 

Subsection 800.154(A) - Revise to read as follows: 

(A) Spaces Used for Environmental Air Cables installed in spaces used for environmental air shall 
be Type CMP. Cables and raceways shall not be installed in ducts or plenums. Abandoned cables shall 
not be permitted to remain. Types CMP, CMR, CMC, CM, and CMX and communications wire 
installed in compliance with 300.22 shall be permitted. Listed plenum communications raceways shall 
be permitted to be installed in spaces used for environmental air as described in 300 22(C) Onlv Tvne 
CMP cable shall be permitted to be installed in raceways. 
Subsection 800.154(F) - Add the following sentence at the end of the subsection: 

Sriciim ° f hybrid P ° Wer and communications ca ble shall be performed by licensed master or special 

ARTICLE 810 

Radio and Television Equipment 

SECTION 81 0.S8 

Subsection 810.58(C) - Replace "14 AWG" with "12 AWG." 



98 



New York City 2011 Electrical Code 



NYC 2011 Electrical Code Technica l Provisions Section 800.2 through Section 830.133 

ARTICLE 820 

Community Antenna Television and Radio D istribution Systems 

SECTION 820.2 

Section 820.2 - Revise the definition of "Abandoned Coaxial Cable" to read as follows: 
Abandoned Coaxial Cable. Installed coaxial cable that is not terminated at equipment other than a 
coaxial connector and not identified for future use with a tag securely fixed to each end and indicating 
the location of the opposing end. 

SECTION 820.25 

Section 820.25 - Revise to read as follows: 

820.25 Abandoned Cables. The accessible portion of abandoned coaxial cables shall be removed. 

Where a coaxial cable is identified for future use with a tag, the tag shall be of sufficient durability. 

SECTION 820.100 

Subsection 820.100(A)(3) - Replace "14 AWG" with "12 AWG." 

SECTION 820.133 

Subsection 820.133(A)(1) Exception No. 1 -Delete the words "non-power-limited fire alarm," 

Subsection 820. 133(A)(l)(a)(2) -Delete 820.133(A)(l)(a)(2) in its entirety. 

Subsection 820.133(A)(2) Exception No. 1 -Delete the words "non-power-limited fire alarm," 

Subsection 820.133(A)(2) - Delete Exception No. 2 in its entirety. 

Subsection 820.133(C) - Add a new subsection 820.133(C) to read as follows: 

(C\ Electric Closets. Television and radio equipment and cabling shall not be installed in Electric Closets. 



SECTION 820.154 

820.154(A) Revise the title to read as follows: 

(A) Spaces Used for Environmental Air. 



New York City 2011 Electrical Code 



99 



Section 800.2 through Section 830.133 NYC 2011 Elect rical Code Technical Provisions 

ARTICLE 830 

Network-Powered Broadband Communications Systems 

SECTION 830.2 

Section 830.2 - Revise the definition of "Abandoned Network-Powered Broadband Communications 
Cable" to read as follows: 

Abandoned Network-Powered Broadband Communications Cable. Installed network-powered 
broadband communications cable that is not terminated at equipment other than a connector and not 
identified for future use with a tag securely fixed to each end and indicating the location of the opposing end. 

SECTION 830.25 

Section 830.25 - Revise the second sentence to read as follows: 

Where a network-powered broadband communications cable is identified for future use with a tag, the 
tag shall be of sufficient durability. 

SECTION 830.100 

Subsection 830.100(A)(3) - Replace "14 AWG" with "12 AWG." 

SECTION 830.133 

Subsection 830.133(A)(l)(b)(2) - Delete the subsection in its entirety. 

Subsection 830.133(A)(1)(d) - Delete the following words from Exception No. 1: "non-power limited 
fire alarm." 

Subsection 830.133(D) - Add a new subsection 830.133(D) to read as follows: 

(D) Electric Closets. Broadband communications equipment and cabling shall not be installed in 
Electric Closets. 